● Excellent flexibility, widely used for the level measurement of fly ash, solid granules and adhesive materials. ● With an external dual color LED indicator and housing with electronics can be rotated during installation to make the orientation of LED indicator convenient for long distance observation. ● Modular design for high reliability, easy installation and maintenance. ● Passed third party reliability tests and received certifications from the third party, guaranteed extreme high reliabi......
Product Details
  • Cape-11AStandard RF Admittance Level Switch can measure capacitance as well asimpedance between probe and vessel. It is suitable for dust and coal ashes levelmeasurement. The probe is not susceptible to material buildup. It is flexiblefor various applications. Cape-11A is with modular design, easy forinstallation and maintenance. External LED light is ideal for long distanceobservation.


  • In Cape-11 RFAdmittance Level Switch series products, a probe is designed to detect thechange of capacitance and impedance between probe and vessel wall to fulfillmaterial level measurement and control. In its electronic unit, reactance between measurement electrode and thewall of an empty vessel constitute a balanced bridge circuit whichoutputs a stable oscillation signal. As medium level rises, measured mediumcovers measurement electrode, reactance between electrode and the wall ofvessel changes. It causes imbalance of bridge circuit and stops the oscillationas a result. A post-circuit is designed to detect the change of output signalfrom bridge circuit and generate an alarm signal. In addition, oscillation signal at radio frequency is not only applied to themeasurement electrode but also applied to a shield pole through a 1: 1voltage-follower, so measurement electrode and shield pole have the sameelectric potential, phase, and frequency, but these two electrodes areinsulated from each other. Even if there is medium buildup on probe, becausethere is no electric potential difference between measurement electrode andshield pole, and the reactance change on shield pole has no effect on thedetection of post-circuit. Therefore, only reactance change on measurementelectrode induced by the filled medium between measurement electrode and thewall of vessel will be detected by post-circuit. It eliminates the effect ofmedium buildup on level measurement.


  • ● Excellent flexibility, widely used for the level measurement of fly ash, solid granules and adhesive materials.
    ● With an external dual color LED indicator and housing with electronics can be rotated during installation to make the orientation of LED indicator convenient for long distance observation.
    ● Modular design for high reliability, easy installation and maintenance.
    ● Passed third party reliability tests and received certifications from the third party, guaranteed extreme high reliability.

    ● Inexpensive with super quality, high cost-effective ratio. 


  • Medium

    Medium Type

    Solid granules and adhesive materials

    Dielectric constant

    ≥1.6

    Probe data

    Probe length

    250~2000mm

    Shield length

    90mm/240mm/300mm /590mm , can also be customized

    Diameter

    φ8mm/φ10mm

    Materials

    External housing

    Aluminum alloy

    Inner housing

    Plastic

    Probe metallic parts

    SUS304, 316L

    Probe insulation parts

    PTFE

    Power supply

    AC

    85~264V AC

    DC

    18~30V DC

    Power consumption

    ≤3W

    Switch delay

    When immersed

    1s

    When laid bare

    1s

    Signal output

    Relay

    DPDT, 8A/250V AC/30V DC

    Relay Delay

    0~30s continuous adjustable

    Operating conditions

    Process temperature

    -40~250℃

    Ambient temperature

    -40~70℃

    Storage and transport temperature

    -40~80℃

    Approvals

    Protection rating

    IP66

  • ● Electrostaticprecipitator bag, ash hopper and conveying pump in ash transport system atpower plant.

    ● Coalash bunker in coal ash collecting device at power plant.

    ● Sootbin and silo in flue gas desulfurization apparatus at power plant.

    ● Limestonesilo in a sintering desulfurization apparatus.