Welcome Customer !

Membership

Winsun Automation Instrumentation Co.Ltd.
Free Member ·1YRS
WuXi,JiangSu
Manufacturer

Main Products: Transducer|Temperature Sensor|Level Transmitter

Xwboo>Products
Product Categories

Winsun Automation Instrumentation Co.Ltd.Free·1YRS

  • E-mail

    wenshengltd@126.com

  • Phone

    86-510-86023568

  • Address

    108# Binhu road, Wuxi, Jiangsu, China

Contact Now

WSLG Turbine Flow Meter

Model
Nature of the Manufacturer
Manufacturer
Product Category
Place of Origin
City, Province
Overview
WSLG Turbine Flow Meter
Product Details

WSLG Turbine Flow Meter

PRODUCT DESCRIPTION

WSLG Liquid turbine flow meter is a new generation turbine flow meter which was designed with advanced flow technologies both home and aboard. The product possesses advantages of simple structure, light in weight, high accuracy, good repeatability, short response time, easy installation, etc. It could be used widely in measurement of closed pipe system for pure liquid that will not react with 1Cr18Ni9Ti, 2Cr13, Al2O3 and hard alloys. Kinematic viscosity of the medium liquid shall be smaller than 5×10-6m2/s.

Measurement for medium with kinematic viscosity larger than 5×10-6m2/s will need calibration with the actual liquid. WSLG series could also operate with specific display instruments for flow control, over flow alarm and many other functions.

FEATURES

Accuracy: Default type: ±1%R, ±0.5%R High accuracy type: ±0.2%R

Good repeatability. Repeatability of the product could reach to 0.05%~0.2% in short term. It is this advantage in repeatability that make the product a good choice in trading measurement.

Pulse frequency output, suitable for total flow measurement and connect to computer. No zero drift and with strong anti- interference performance;

Could output high frequency signal (3~4kHz) with high resolution;

Wide range ratio, middle and large diameter could reach to 1:20 and small diameter could reach to 1:10; Compact and light structure, easy for installation and maintenance;

Suitable for high pressure measurement. Since there is no opening on housing of the product, it could be used as a high pressure instrument.

Could operate with multiple sensors. According to requirement of the users, WSLG offers options with different special sensors, for example low temperature type, dual flow direction type, well type, sandy medium type, etc.;

Offer insertion type for large diameter measurement. The insertion type possesses advantages of small pressure loss, low cost and easy installation and maintenance (could be taken out of the pipe without shut the system down).

SPECIFICATIONS

Medium

Non-corrosive low velocity liquid without impurity.

medium

Not suitable for gas and steam

Accuracy

Class 1.0, class 0.5

Flange standard

GB/T 9119-2010, DIN, ANSI, JIS

Output

Pulse, 4-20mA analog output, RS485 (Modbus-RTU protocol), HART, communication.

Diameter and installation

Flange connection DN15-DN200 Screw connection: DN4-DN50

Loose flange connection: DN4-DN200

Medium temperature

Default type T1: -20℃~+80℃ ( Standard) High temp. type T2: -20℃~+120℃ (OEM) High temp. type T3: -20℃~+150℃(OEM)

Operation condition

Operating temperature: -20℃~+60℃ Related humidity: 5%~90% Atmospheric pressure: 86kPa~106kPa

Ingress protection

IP65

Explosion proof

ExdIIBT6 (explosion proof type)

Flow range

Diameter (mm)

Standard flow range (m3/h)

Extended flow range (m3/h)

Conventional endurance pressure (m3/h)

4

0.04~0.25

0.04~0.4

1.6MPa

6

0.1~0.6

0.06~0.6

1.6MPa

10

0.2~1.2

0.15~1.5

1.6MPa

15

0.6~6

0.4~8

1.6MPa

20

0.8~8

0.45~9

1.6MPa

25

1~10

0.5~10

1.6MPa

32

1.5~15

0.8~15

1.6MPa

40

2~20

1~20

1.6MPa

50

4~40

2~40

1.6MPa

65

7~70

4~70

1.6MPa

80

10~100

7~100

1.6MPa

100

20~200

10~200

1.6MPa

125

25~250

13~250

1.6MPa

150

30~300

15~300

1.6MPa

200

80~800

40~800

1.6MPa

TYPE SELECTION

WSLG-

Note

Diameter

DNXX

DN4~DN200mm

Converter Type

N1

24VDC,Pulse output,No display

N2

24VDC,Pulse output,No display,EX

A

24VDC,4-20mA output,No display,EX

E1

Battery power supply,No output,Digital display,EX

E2

24VDC,Pulse and 4-20mA output,RS485,Digital display,EX

E2+B

24VDC+battery power supply,Pulse and 4-20mA output,RS485, Digital display,EX

E3

24VDC,Pulse and 0-20mA output,RS485,Digital display,EX

E3+B

24VDC+battery power supply,Pulse and 0-20mA output,RS485, Digital display,EX

E+H

24VDC,4-20mA output,HART,Digital display,EX

G5

220VAC,Pulse and 4-20mA output,RS485,Digital display,EX

G6

220VAC,Pulse and 0-20mA output,RS485,Digital display,EX

Accuracy

10

±1.0%R

05

±0.5%R

Flow Range

S

Standard Range

E

Extended Range

Body Material

S4

SS304

S6

SS316

Explosion-Proof

BT

Exd II BT6

NA

None

Connection

THM

External thread,Apply to DN4~DN50mm

THF

Internal thread,Apply to DN4~DN50mm

WAF

Flange clamp

DXX

D16:DIN PN16 Flange;D25:DIN PN25 Flange

AXX

A15:ANSI 150# Flange;A30:ANSI 300# Flange

JXX

J10:JIS 10K Flange;J20:JIS 20K Flange

Temperature

T1

-20~+80℃

T2

-20~+120℃

T3

-20~+150℃