1: Product Features and Uses
This product is suitable for transmission lines for automatic control or monitoring systems with an AC rated voltage of 450 / 750V and below, electrical appliances and instrumentation.
Low-smoke halogen-free polyolefin has a small amount of smoke when burned and releases halogen-free acid gas. It is an environmentally-friendly cable and is suitable for occasions with special requirements for fire protection.
Two: product implementation standards
GB9330-88
Flame retardant performance test executes GB12666-90 standard
Three: Use characteristics
1. AC rated voltage: U0 / U 450 / 750KV
2. Maximum working temperature: polyvinyl chloride (polyethylene) insulation does not exceed 70℃
XLPE insulation 90℃
Low-smoke halogen-free flame-retardant polyolefin 70℃
Low-smoke halogen-free flame-retardant cross-linked polyolefins at 90 ℃ and 125 ℃
3. Minimum ambient temperature: PVC sheath: fixed laying -40℃, non-fixed laying -15℃
4. The cable installation temperature should not be lower than 0℃.
5. Cable allowable bending radius: minimum 6 times of cable outer diameter for unarmored cable
Copper tape shielded or steel tape armored cable is at least 12 times the outer diameter of the cable