XD371XThe type pn10-pn16 double clip signal butterfly valve is suitable for the occasions where the valve is normally open in the fire control system. When the valve is opened or closed to the designated position, the signal device on the valve can send a signal to the fire detection center to show whether the butterfly valve is open or closed, so as to prevent the valve from being closed by mistake and affecting the automatic sprinkler function.
Product description
XD371XThe type pn10-pn16 double clip signal butterfly valve is suitable for the occasions where the control valve in the fire control system is required to be normally open. When the valve is opened or closed to the designated position, the signal device on the valve can send a signal to the fire detection center to show the butterfly valve is open or closed, so as to prevent the valve from being closed by mistake and affecting the automatic sprinkler function。
performance parameter
XD371XPerformance parameters of PN10 ~ PN16 butterfly valve
| model | XD371X-10 | | | | XD371X-16 |
| working pressure(MPa) | 1.0 | | | | 1.6 |
| Applicable temperature(℃) | ≤65 |
| Applicable media | Water, etc |
| Material Science | valve body | cast iron |
| Disc | Ductile iron (nylon coating on the surface)) |
| Stem | Chromium stainless steel |
| valve seat | Butadiene rubber |
| filler | O-ring | | |
Connection size
XD371XDimensions of PN10 ~ PN16 butterfly valve| XD71X-10 |
| Diameter(mm) | L | D | K | n-Фd | H | H1 | W | W1 |
| 50 | 43 | 165 | 125 | 4-Ф18 | 80 | 320 | 266 | 90 |
| 65 | 46 | 185 | 145 | 4-Ф18 | 89 | 330 | 266 | 90 |
| 80 | 46 | 200 | 160 | 8-Ф18 | 95 | 340 | 266 | 90 |
| 100 | 52 | 220 | 180 | 8-Ф18 | 114 | 360 | 266 | 90 |
| 125 | 56 | 250 | 210 | 8-Ф18 | 127 | 380 | 266 | 90 |
| 150 | 56 | 285 | 240 | 8-Ф22 | 139 | 390 | 266 | 90 |
| 200 | 60 | 340 | 295 | 8-Ф22 | 175 | 525 | 125 | 90 |
| 250 | 68 | 395 | 350 | 12-Ф22 | 203 | 555 | 125 | 90 |
| 300 | 78 | 445 | 400 | 12-Ф22 | 242 | 610 | 190 | 90 |
尺寸图
matters needing attention
1. The signal butterfly valve can be installed on the pipeline at any position in space.
2. The installation position of butterfly valve shall ensure the convenience of use, maintenance and replacement.
3. The butterfly valve can be installed without considering the flow direction of pipeline medium, that is to allow two-way flow.
4. Before installation, the butterfly valve should be stored in a dry place in the room, and the valve plate should be slightly opened 4 ° to 5 °.
5. Before installation, the following work shall be carried out:
a. Carefully check whether the service condition is consistent with the performance specification of this butterfly valve.
b. Clean the inner cavity and sealing surface. Do not open or close the butterfly plate before cleaning.
c. Check whether the transmission device is connected with the flange on the butterfly valve.
6. When the butterfly valve is clamped in the pipeline, pay attention to whether the connection force is uniform.
7. After the butterfly valve is installed, the valve plate must be in the open position during the pipeline strength test.
8. After installation, the butterfly valve shall be inspected regularly, and the main inspection items are as follows:
a. Check whether the butterfly valve seat and O-ring are damaged.
b. Sealing performance of valve plate sealing surface.
c. After the butterfly valve is overhauled and assembled, there shall be no jamming during the opening and closing rotation.
d. After repair and assembly of butterfly valve, sealing performance test shall be conducted as required.
f. After each overhaul, detailed records shall be made for reference.