Low Smoke No Halogen Flame Retardant Fire Resistant Cable
The product is used for controlling and supervising return circuit or power system with requirement of rated voltage 600/1000V or lower, low smoke and no halogen,
Executive Standard:
Use enterprise standard or refer to GB9330-88, GB/T12706-2002 standard.
Working condition
- Long-term working temperature of cable is 90℃
- Cable insulation temperature is no less than 0℃. Recommended bending radius is as following:
No halogen flame retardant control cable:
- Bending radius is no less than 12 times that of cable outer diameter for cable with structure of armoring and copper tape shielding
- Bending radius is no less than 6 times that of cable outer diameter for cable with other structure
No halogen flame retardant power cable:
- Bending radius is no less than 20 times that of cable outer diameter for cable with single core
- Bending radius is no less than 15 times that of cable outer diameter for cable with multi cores
Cable Type & Name
Type | Name |
| Copper core | Aluminum core |
| WDZ-YJY | WDZ-YJLY | Copper core (aluminum core) XLPE insulation low smoke no halogen flame retardant power cable |
| WDZ-YJY23 | WDZ-YJLY23 | Copper core (aluminum core) XLPE insulation steel tape armoring low smoke no halogen flame retardant power cable |
| WDZ-YJY33 | WDZ-YJLY33 | Copper core (aluminum core) XLPE insulation thin steel wire armoring low smoke no halogen flame retardant power cable |
| EDZN-YJY | / | Copper core XLPE insulation low smoke no halogen flame retardant fire resistant power cable |
| WDZN-YJY23 | / | Copper core XLPE insulation steel tape armoring low smoke no halogen flame retardant fire resistant power cable |
| WDZN-YJY33 | / | Copper core XLPE insulation thin steel wire armoring low smoke no halogen flame retardant fire resistant power cable |
| Type | Name |
| WDZ-KYJY | Copper core XLPE insulation low smoke no halogen flame retardant control cable |
| WDZ-KYJYP | Copper core XLPE insulation copper wire shielding low smoke no halogen flame retardant control cable |
| WDZ-KYJYP2 | Copper core XLPE insulation copper tape shielding low smoke no halogen flame retardant control cable |
| WDZ-KYJYP2-23 | Copper core XLPE insulation copper tape shielding steel tape armoring low smoke no halogen flame retardant control cable |
| WDZ-KYJY33 | Copper core XLPE insulation thin steel wire armoring low smoke no halogen flame retardant control cable |
| WDZN-KYJY | Copper core XLPE insulation low smoke no halogen flame retardant fire resistant control cable |
| WDZN-KYJYP2 | Copper core XLPE insulation copper tape shielding low smoke no halogen flame retardant fire resistant control cable |
| WDZN-KYJYP2-23 | Copper core XLPE insulation copper tape shielding steel tape armoring low smoke no halogen flame retardant fire resistant control cable |
Main technical parameter:
- Conductor DC resistance is in accordance with GB/T3956 standard
- Insulated resistance constant is no less than 3.67MΩ.km at 90℃. Volume resistance ratio is no less than 1012Ω.Cm
- Cable shall endure 3.5kv A.C. voltage test for 5 minutes without puncture
- Performance target of no halogen, low smoke and flame retardant.
| Test item | Unit | Requirement | Teat method |
| Smoke density test Min. permeate ratio | % | 60 | GB/T17651-1998 |
| Corrosive test Min. PH value Max. conductive ratio | µ S/mm | 4.3 10 | GB/T17650.2-1998(idtIEC60754) |
| Hydrogen halogen gas content | Mg/g | ≤5 | GB/T17650.1-1998(idtIEC60754) |
| Bundle burning test Test class Time for fire Total volume of combustible per meter Carbide height | Min L m | A B C 40 40 2 7 3.5 1.5 2.5 2.5 2.5 | GB/T18380.3-2001(replace for GB12666.5-90) |