Mining Flame Retardant Portable Flexible Cable with Rated Voltage of 0.66/1.14kV or Lower for Coal Mine
Application:
The product is copper core flexible cable with A.C. rated voltage of 0.66/1.14 or lower for core mine moving equipment purpose.
Executive standard:
Flame retardant flexible cable for coal mine application Part 1 general regulation.
Flame retardant soft cable for coal mine application Part 5 flexible cable with rated voltage of 0.66/1.14 kV or lower.
Test methods and judging rules of flame retardant performance of flame retardant cable for the coal mine application.
Type & Description
Type | Description | Application |
| MY-0.38/0.66kV | rubber jacketed flexible cable for coal mine application | The cable is used to connect power supply of all kinds of mining equipment under well with rated voltage of 0.38/0.66kV |
| MYE-0.38/0.66kV | elastomer flexible cable for coal mine application |
| MYP-0.38/0.66kV | shielding rubber jacketed flexible cable for coal mine application |
| MYPE-0.38/0.66kV | shielding elastomer flexible cable for coal mine application |
| MYP-0.66/1.14kV | shielding rubber jacketed flexible cable for coal mine application | The cable is used to connect power supply of all kinds of mining equipment under well with rated voltage of 0.66/1.14kV |
| MYPE-0.66/1.14kV | shielding elastomer flexible cable for coal mine application |
Main technical parameter:
- Conductor DC resistance at 20℃
Resistance of each core conductor shall meet the requirements of class 5 conductor (multi-stranded flexible structure) stipulated in GB/T3956 standard at 20℃
- Insulated resistance at 20℃
Insulated volume resistance ratio of elastomer insulated power core is at least more than 1.0*1013Ω.cm; insulated resistance of rubber insulation power core shall meet the requirements stipulated in the following table.
| Nominal cross section area of power core (mm2) | Insulated resistance at 20℃(MΩ.km) | Nominal cross section area of power core(mm2) | Insulated resistance at 20℃(MΩ.km) |
| 4 | ≥200 | 95 | ≥80 |
| 6 | ≥180 | 120 | ≥50 |
| 10 | ≥160 | 150 |
| 16 | ≥120 | 185 |
| 25 | ≥120 | 240 |
| 35 | ≥100 | 300 |
| 50 | ≥100 | 400 |
| 70 | ≥80 | |
- A.C. voltage test
Insulated power core of cable shall endure following A.C. voltage test without puncture.
Rated voltageU0/U (kV) | Test voltage (effective value) (kV) | Time for giving pressure (min) |
| 0.38/0.66 | 3.0 | 5 |
| 0.66/1.14 | 3.7 |
4. Flame retardant performance of finished cable can meet all kinds of test requirements stipulated in MT386 standard.