PVC Insulation & Sheath Power Cable of 0.6/1 kV or Lower
It is used to transmit and distribute power on the power line of A.C. rated voltage 0.6/1kV
Executive standard:
GB/T12706.1 (equal to the standard of IEC60502)
Working condition:
- Long-term working temperature allowed by cable conductor shall be no more than 70℃
- Max. temperature of cable conductor shall be no more than 160℃ during short circuit(the longest lasting time shall be no more than 5 seconds).
- Environment temperature for installation shall be no less than 0℃
Type, Description and Application occasion
Type | Description | Application occasion |
| Cu | Al |
| VV | VLV | Power cable with PVC insulation and sheath | To be laid indoors, in the tunnel, cable furrow or pipe. The cable can not bear mechanical force from outside |
| VV22 | VLV22 | Power cable with PVC insulation, PVC sheath and steel tape armored | To be laid underground, the cable can bear certain mechanical force, but it can not bear great pulling force |
Production Scope
Type | Core number | Nominal cross section area |
| Cu | Al |
| VV -- VV22 | -- VLV VLV22 | 1 | 1.5~500 2.5~500 10~500 |
| VV -- VV22 | -- VLV VLV22 | 2 | 1.5~185 2.5~185 4~185 |
| VV -- VV22 | -- VLV VLV22 | 3 | 1.5~300 2.5~300 4~300 |
| VV -- VV22 | -- VLV VLV22 | 4 | 2.5~300 2.5~300 4~300 |
| VV VV22 | VLV VLV22 | 3+1 | 4~300 4~300 |
Main technical parameter of cable:
- Max. value of conductor DC resistance shall meet the requirement of conductor of category 2 stipulated in GB/T3956 standard at 20℃
- For single core cable without shielding, voltage test of 3.5kV under power frequency is put on for 5 minutes between conductor and water when be immersed in the water for one hour. For multi-core cable, between each insulated conductor and other conductor, voltage test of 3.5kV under power frequency is put on for 5 minutes without puncture of insulation.