1.Designed floating charging service life: 12 years(25ºC)
2.Sealed and maintenance free operation
3.Safety valve installation for explosion proof
4.Low self-discharge characteristic
5.Wide operating temperature range from -20°C to +45°C
6.Lead-calcium alloy with Sn, Prevent corrosion
7.The vrla battery have passed ISO9001 and CE certificates
| Battery Model No. | FBR12V120FT |
| Nominal Voltage | 12V |
Capacity (25ºC) | 20HR(5.25V) | 120Ah |
| 10HR(5.25V) | 105Ah |
| 1HR(4.80V) | 72Ah |
| Dimension | Length | 551±2mm |
| Width | 110±2mm |
| Height | 239±2mm |
| Total height | 239±2mm |
| Approx. Weight | 36kg±4% |
| Terminal type | F13 |
Internal resistance (Fully charged,25ºC) | Approx 5mΩ |
Capacity affected by temperature(20HR) | 40ºC | 102% |
| 25ºC | 99% |
| 0ºC | 85% |
| -15ºC | 65% |
Self-discharge (25ºC) | 3month | Remaining Capacity:91% |
| 6month | Remaining Capacity:82% |
| 12month | Remaining Capacity:65% |
| Nominal operating temperature | 25ºC±3ºC(77ºF±5ºF) |
Operating temperature range | Discharge | -15ºC-50ºC(5ºF-122ºF) |
| Charge | -10ºC-50ºC(14ºF-122ºF) |
| Storage | -20ºC-50ºC(-4ºF-122ºF) |
Float charging voltage (25ºC) | 13.5 to 13.8V Temperature compensation:-18mV/ºC |
Cyclic charging voltage (25ºC) | 14.5 to 15V Temperature compensation:-30mV/ºC |
| Max charging current | 36A |
| Max discharging current | 960A(5sec.) |
| Designed floating life(20ºC) | 12years |
1. Solar and wind energy storage system
2. EPS and UPS battery backup
3. Signal system , emergency lighting system , security system
4. Telecommunication Equipment
5. Power source for portable devices or tools.