Water Chiller Specification
Model Item | AC-2 | AC-3 | AC-5 | AC-6 | AC-8 | AC-10 | AC-12 | AC-15 | AC-20 | AC-25 | AC-30 | AC-40 | AC-50 |
| Nominal cooling Capacity | Kcal/h 50HZ/60HZ | 5332 | 7955 | 12126 | 14706 | 19522 | 25886 | 30014 | 38012 | 51772 | 60028 | 76024 | 103544 | 120056 |
| 6398 | 9546 | 14551 | 17647 | 23426 | 31063 | 36017 | 45614 | 62126 | 72034 | 91229 | 124253 | 144067 |
KW 50HZ/60HZ | 6.2 | 8.5 | 14.5 | 17.1 | 22.7 | 29 | 36.5 | 43.5 | 58 | 73 | 92.7 | 123.6 | 146 |
| 4.10 | 7.44 | 13.62 | 17.40 | 20.40 | 27.24 | 37.10 | 40.86 | 54.48 | 74.20 | 85.50 | 114.00 | 148.40 |
| Input power | KW | 2.25 | 3.2 | 5.53 | 5.93 | 8.08 | 11.22 | 12.32 | 15.8 | 21.36 | 23.56 | 31.36 | 39.6 | 46.72 |
| Power supply | 1P220V 50/60HZ | 3PH~380V 50HZ(200V/220V/415V /460V 50HZ/60HZ) |
| (110V 50HZ/60HZ) |
| Refrigerant | type | R22(R134A/407C/R410A) |
| type of control | capillary | Expansion valve |
| Compressor | type | hermetic rotary | Hermetic scroll type (piston) |
| power(kw) | 1.73 | 2.64 | 4.4 | 4.8 | 6.1 | 8.8 | 9.9 | 13.2 | 17.6 | 19.8 | 24.6 | 32.8 | 39.6 |
| condenser | type | High efficient finned copper tube + low noise outer rotor fan |
| Power(kw) | 0.15 | 0.19 | 0.38 | 0.38 | 0.48 | 0.92 | 0.92 | 1.1 | 1.56 | 1.56 | 2.76 | 2.8 | 3.12 |
| cooling air flow(m3/h) | 2000 | 3000 | 5000 | 6000 | 8000 | 10000 | 12000 | 15000 | 20000 | 25000 | 30000 | 40000 | 50000 |
| Evaporator | type | shell and tube+water tank |
| chilled fluid flow(m3/h) | 1.07 | 1.47 | 2.50 | 2.95 | 3.91 | 5.00 | 6.29 | 7.50 | 10.00 | 12.59 | 15.98 | 21.31 | 25.17 |
| 0.71 | 1.28 | 2.35 | 3.00 | 3.52 | 4.70 | 6.40 | 7.04 | 9.39 | 12.79 | 14.74 | 19.66 | 25.59 |
| Volume(L) | 22 | 50 | 60 | 75 | 120 | 200 | 200 | 300 | 350 | 350 | 460 | 580 | 620 |
| inlet and outlet pipe diameter (inch) | 1/2" | 1" | 1" | 1" | 1-1/2" | 1-1/2" | 2" | 2" | 2" | 2-1/2" | 2-1/2" | 2-1/2" | 3" |
| water pump | power (kw) | 0.37 | 0.37 | 0.75 | 0.75 | 1.5 | 1.5 | 1.5 | 1.5 | 2.2 | 2.2 | 4 | 4 | 4 |
| lift(m) | 20 | 20 | 20 | 20 | 20 | 20 | 20 | 20 | 20 | 20 | 22 | 22 | 22 |
| safety protection | compressor overheating protection, over-current protection, high and low pressure,over-temperature protection, flow switch, protection,phase sequence or missing phase protection, exhaust overheating protection |
| dimension | L(mm) | 750 | 930(1200) | 1140(1300) | 1140(1300) | 1530(1600) | 1530(1600) | 1530(1600) | 1850(1900) | 2150(2200) | 2150(2200) | 2150(2350) | 2100(2350) | 2350 |
| W(mm) | 500 | 520(560) | 560(650) | 560(650) | 780(850) | 780(850) | 780(850) | 990(1050) | 1130(1300) | 1130(1300) | 1480(1480) | 1660(1800) | 1760 |
| H(mm) | 948 | 1185(1280) | 1250(1380) | 1250(1380) | 1630(1810) | 1630(1810) | 1630(1810) | 1870(1960) | 1820(2020) | 2000(2020) | 1950(1900) | 2100(2150) | 2100 |
| weight | Kg | 100 | 135 | 175 | 180 | 310 | 450 | 530 | 750 | 835 | 920 | 1150 | 1250 | 1450 |
Note:
1.Nominal cooling capacity is according to:
Inlet chilled fluid temperature: 17℃
Outlet chilled fluid temperature: 12℃
Inlet cooling air temperature: 30℃
Outlet cooling air temperature: 35℃
2. Working Range:
The temperature range of chilled fluid is from 5℃ to 35℃;
Temperature difference between inlet and outlet chilled fluid is from 3℃ to 8℃.
It is better to run the chiller while the ambient temperature at or below 35℃.
We reserve the right to modify the above dimensions or parameters without further notice.