NTGseries industrialcooling toweris available in capacity for single cell from 800 tons to 5000 tons, various modular combinations are designed to meet different requirements. The cooling tower is highly used in Pharmaceutical industry, Metail casting, Paper industry, Steel plant, Cement factory, Power plant, Petrochemical industry, Sugar factory, ect.

Features
♦ Space saving, light-duty structures ♦ Energy saving, low noise ♦ Perfect corrosion resistance ♦ Convenient combination and easy maintenance |  |
Components Instruction
Structure
NTG Series cooling tower shall be proposed in compliance with the specification of cooling tower for this job, All framework and structural members shall be constructed of Reinforced Concrete (supplied by customer) / of Hot-dip Galvanized Steel (supplied by vender) , to provide maximum strength and durability.
Fan Stack
The FRP velocity recovery fan stack is used in the proposed cooling tower. This profile of fan stack is designed on basis of the theory of air channel uniformity. It will guide the air flow exit vertically which will reduce the effect of re-circulation and also reduce the noise level.
Distribution system
Using the unique overflow device to realize smooth and even water distribution under different sustem load, the device completely eliminates the drift loss of coolig tower. Hot water basin cover avoids water pollution by foreign objects falling into hot basin. Meantime, it avoids direct sunlight and inhabit growth of algae.
Fill Packing
Used high quality & improved performance PVC with good material, it is high cooling efficiency and anti-corrosive & UL V-0. Brand new PVC materials, integrated eliminators and louvers. The infills are hanging type, environmental friendly and big coefficient of heat transfer, good hydrophilicity. Small wind resistance, high ventilation performance. Special material for option if high entering water temperature.
Frame structure and fasteners
Leading structure design and high-quality materials to make frame structure and fasteners, the standard configuration of structure and fasteners is superior hot-dip galvanized steel, good anti-corrosion, design lifespan is more than 15 years. Stainless steel or F.R.P frame structure available for poor water soltion, and SUS304 or SUS316L for fasteners.
Optional Accessories
♦ Noise reduction upgrade ♦ Anti-Freeze heater
♦ Vibration isolator & rubber mat ♦ Stainless steel framework / bolts and nuts (304 / 316)
♦ High-temperature upgrade ♦ Dual-speed Motor & VFD motorAnti-Freeze heater Technical Specification of NTG Series Cooling Tower | Item | Water Flow (m3/h) | Cooling Capacity Kcal/h | Dimention (mm) | Fan | Water Pressure (x10⁴Kpa) | Weight (kg) |
| Model | Length | Width | Height | Diameter (mm) | Power (Kw) | Dry | Wet |
| NTG-800 | 800 | 8.0x10⁶ | 7400 | 7400 | 7800 | 4700 | 30 | 8.0 | 11.63 | 18.45 |
| NTG-1000 | 1000 | 1.0x10⁷ | 9000 | 9000 | 8700 | 5460 | 45 | 8.8 | 19.68 | 31.23 |
| NTG-1500 | 1500 | 1.5x10⁷ | 10500 | 10500 | 9500 | 6000 | 55 | 10.0 | 29.34 | 46.75 |
| NTG-2000 | 2000 | 2.0x10⁷ | 12000 | 12000 | 10200 | 7700 | 90 | 11.0 | 45.03 | 68.69 |
| NTG-2500 | 2500 | 2.5x10⁷ | 13500 | 13500 | 10700 | 8000 | 132 | 11.5 | 46.20 | 75.30 |
| NTG-3000 | 3000 | 3.0x10⁷ | 15000 | 15000 | 11400 | 8530 | 160 | 12.0 | 65.00 | 99.20 |
| NTG-3500 | 3500 | 3.5x10⁷ | 16000 | 16000 | 12100 | 9140 | 160 | 13.3 | 76.05 | 104.80 |
| NTG-4000 | 4000 | 4.0x10⁷ | 17400 | 17400 | 12400 | 9140 | 200 | 13.5 | 78.50 | 132.00 |
| NTG-5000 | 5000 | 5.0x10⁷ | 18380 | 18380 | 13900 | 10300 | 250 | 14.5 | 85.50 | 139.50 |

|
| Casing | Fiberglass Reinforced Polyester (F.R.P) |
| Frame | H.D.G.S / Stainless steel / Concrete |
| Motor | Enclosed, IP 55, F class |
| Fan stack | Fiberglass Reinforced Polyester (F.R.P) |
| Handrail and cage | H.D.G.S |
| Infill | Fire retardant P.V.C |
| Drift eliminator | Fire retardant P.V.C |
| Distribution system | H.D.G.S & P.V.C |
| Clapboard | Fiberglass Reinforced Polyester |
| Basin | Concrete (by others) |