Ultrasonic sensors present the ideal solution for non-contact position and distance measurement in all industrial areas where environmental conditions such as dust, smoke or steam may affect the sensors. Objects consisting of a variety of materials can be detected to within millimeters regardless of color or shape.
The ultrasonic sensor produces a data carrier utilizing very high frequencies that are outside the human’s audible range. The time it takes for that ultrasonic wave to pass between the sensor and the object is the value for the distance or the position.
Ultrasonic sensors have proven their reliability and precision in many industries and applications, including:
lumber and furniture
construction materials and equipment
farming equipment
level control applications
Brife introduction of ultrasonic sensor
Ultrasonic sensors present the ideal solution for non-contact position and distance measurement in all industrial areas where environmental conditions such as dust, smoke or steam may affect the sensors. Objects consisting of a variety of materials can be detected to within millimeters regardless of color or shape.
The ultrasonic sensor produces a data carrier utilizing very high frequencies that are outside the human’s audible range. The time it takes for that ultrasonic wave to pass between the sensor and the object is the value for the distance or the position.
Ultrasonic sensors have proven their reliability and precision in many industries and applications, including:
lumber and furniture
construction materials and equipment
farming equipment
level control applications
Technical data
General Specifications
Sensing distance 80…2000mm
Adjustment range 120…2000mm
Unusable area 0…80mm
Standard target plate 100mm×100mm
Transducer frequency About 180kHz
Response delay About 195ms
Indicators/Operating means
LED blue Power on
LED yellow indication of the switching state Flashing:program function object detected
LED red permanently red: Error Red, flashing:program function, object not detected
Electrical specifications
Operating voltage UB 10…30VDC,ripple10%ss
Power consumption P0 ≤900 mW
Output
Output type 1 analogue output 4…20mA
Resolution evaluation range [mm]/4000, but ≥ 0.35 mm
Deviation of the characteristic curve ≤0.2% of full-scale value