4P 100A-3150A HGLC side load isolate switch Low Voltage Disconnector Switch

Model
Nature of the Manufacturer
Manufacturer
Product Category
Automatic Transfer Switch
Place of Origin
City, Province
Overview
load breaker switch1.crruent reach 3150A2.can provide matching iron box 3. copper T2 material 4. Flame retardant V0
Product Details

4P 100A-3150A HGLC side load isolate switch Low Voltage Disconnector Switch

Low voltage ac isolator switch rated voltage 400V/690V, rated current 1600A, 3 poles & 4 poles, The shell made of glass fiber reinforced unsaturated polyester resin has good flame retardancy, joint performance, carbonation resistance and impact resistance.

Optional Indoor Operation Or Outdoor Operation

Modular design

The terminal is Copper T3

Flame retardant V0 grade plastic

Observation window on the front

Avoid erroneous operations

Conventional Current1600A3150A
Rated Current In (A)100012501600200025003150
Rated Insulation Voltage Ui (V)10001000
Dielectric Strength (V)1000010000
Rated Working Current AC-21B100012501600200025003150
380VAC-22B100012501600200025003150
AC-23B
AC-21B100010001600200025002500
660VAC-22B800800800100012501600
AC-23B
Motor Power380V560560560710710710
P (Kw)660V475475475750750750
Rated Short-Time Withstand Current Lcw (KA Rms) 0.1s/1s505050505050
Rated Breaking Capability Icn (A Rms) AC23 380V300037504800600075009450
Rated Making Capability Icm (A Rms) AC23 380V300037504800600075009450
Rated Shortcurrent Making CapabilityIcm (KA Peak Value)707070105105105
Mechanical Durability 380V500500500300300300
Electical Curability 380V100100100100100100
Operation Moment (Nm)373760606060
Weight (Kg)3 Poles10.510.51625.525.531
4 Poles13132037.537.551.5

Low voltage ac isolator switch live working should be monitored by special personnel. Use tools with insulated handles, stand on dry insulation during work, wear insulated gloves and helmets, wear long-sleeved clothes, and use trowels, metal rulers and metal wool. Brush, donkey and other tools.

When working on the low-voltage strip line that is erected on the high and low voltages, check the distance from the high-voltage line and take measures to prevent accidental contact with high-voltage live equipment.