CMW1 1000A 3P Fixed Intelligent Low Voltage Power Circuit Breakers

Model
Nature of the Manufacturer
Manufacturer
Product Category
Air Circuit Breaker
Place of Origin
City, Province
Overview
Functions of Air Circuit Breaker are:It opens or closes a circuit automatically or manually.Open circuit automatically when a fault take place such as over current, short circuit, earth fault, over frequency,etc.It dampens the arcing in case of ov
Product Details

Type Selection Guide

CMW120003P400AFAC230VHorizontal wiring
Product codeFrame sizePole numberCurrent classInstallation codeCode of control circuit source voltageConnection mode
Conventional
circuit breaker
2000
3200
6300
3P: three-pole
4P: four-pole
400A2500AD: drawout type
F: fixed type
AC230V
AC400V
DC220V
DC110V
Horizontal wiring
Vertical wiring
630A2900A
800A3200A
1000A3900A
1250A4000A
1600A5000A
2000A6300A

Type Selection of Standard Parts and Optional Accessories

M type230V230V230V6 NO 6 NC
Model of
controller
Voltage of
shunt release
Voltage of energy
releasing electromagnet
Voltage of electric
operating mechanism
Auxiliary contact
AA type 2H type
3B2 type 3H type
AC230VAC230VAC230VStandard: 6NO6 NC
recommended
AC400VAC400VAC400V
DC220VDC220VDC220V
DC110VDC110VDC110V
Undervoltage protectionMechanical interlockingOpening lockingDual-power interlockingAccessories
Undervoltage release
Undervoltage instantaneous release
Undervoltage time-delay
release: D1s D3s D5s
Horizontal interlocking
(wirerope interlocking)
Vertical interlocking
(wirerope interlocking)
One lock one key
Two locks one key
Three locks two keys
Five locks three keys
Intelligent horizontal
interlocking
Doorframe
Phase partition
Phase partition strip
AC230VDC220V
AC400VDC110V

Note: mark V in □ if need the corresponding optional accessory

Operating Characteristics

EKA1-2000/3P 400A F AC230V (fixed type 3-pole 400A voltage of control circuit (230V) default horizontal wiring, rated voltage 400V, M type controller, shunt 230V, electric operating mechanism 230V, standard 6 NO 6 NC contacts. Please specify according to the above table if need other accessories.

Model Guide of Intelligent Controller

ConfigurationModel
M2H3B23H
Protection functions●●●●
Overload long delay (L)●●●●
Short-circuit short delay (S)●●●●
Short-circuit instantaneous (I)●●●●
Ground fault (G)/alarm●●●●
Neutral line overcurrent protection (N)○●●●
Current unbalance protection○●●●
Load monitoring(Load)(1)□●□●
Making current protection (MCR)(2)□○□●
Out-of-limit tripping (HSIOC)○○○○
Leakage protection/alarm®(3)—□□□
Required current protection———●
Overvoltage/undervoltage protection—●●●
Voltage unbalance protection—●●●
Reverse power protection———●
Required power protection———●
Overfrequency/underfrequency protection———●
Phase-sequence protection— ●
Measurement functions
Real-time current value, maximum measured value●●●●
Required current measurement———●
Current harmonics, waveform measurement———●
Real-time voltage value, maximum measured value—●●●
Voltage harmonics, waveform measurement———●
Power / power factor measurement——●●
Energy measurement———●
Required power measurement———●
Voltage frequency measurement—●●●
Hot melt measurement—●●●
Circuit breaker contact equivalent measurement—●●●
Auxiliary functions
Long delay protection curve selection○●●●
Fault / alarm log (and query)●●●●
Test function●●●●
Self-test and alarm functions●●●●
Circuit breaker opening/closing (operation) records(3)—□□●
Protection parameter lockout●●●●
Zone interlocking (ZSI) function(4)——□
Communication function—●□●

●Standard configuration ○Auxiliary configuration — No configuration
□Functions that can be added to the standard configuration with appropriate hardware

Main Performance Indexes

CMW1-2000CMW1-3200CMW1-6300
Frame size rated current Inm (A)200032006300
Pole number3,43,43,43
Rated current In (A)400, 630, 800,1000
2000, 2500
2900, 3200
4000, 50006300
Rated voltage Ue (V)400, 690400690400, 690400690
Insulation voltage Ui (V)1000100010001000
Impulse withstand voltage Uimp (V)120001200080008000
Power frequency withstand voltage U (V)AC3500 50HZAC3500 50HZAC3500 50HZAC3500 50HZ
Rated current of N-pole IN (A)50%ln50%ln50%ln,99%ln50%ln,99%ln
Ultimate breakingAC400V80100120120
capacity lcu (kA)AC690V50658585
Running breakingAC400V5080100100
capacity lcs (kA)AC690V40657575
Short-current makingAC400V176220264264
capacity lcm (kA)AC690V105143165165
Short-time withstandAC400V5080100100
current(1s)(RMS) lcw (kA)AC690V40507575
Closing time (ms)70 (max)70 (max)70 (max)70 (max)
Operating
performance
AC400V65003000500500
AC690V30001500500500
Maintenance free150001000040004000
Maintenance required300002000080008000
Connection modeHorizontal verticalHorizontal verticalHorizontalHorizontal
Overall dim. H(height)
×W(width)×L(thickness)
Fixed type 3P402 x 362 x 323402 x 422 x 323——
Fixed type 4P402 x 457 x 323402 x 537 x 323——
Drawout type 3P432 x 375 x 421432 x 435 x 421432 x 813 x 494432 x 928 x 494
Drawout type 4P432 x 470 x 421432 x 550 x 421432 x 928 x 494—

Overall and Mounting Dimensions

Outline and installation dimensions of fixed type circuit breaker, see Fig.10, 11

eka1 air circuit breaker 1