CX-FS-FR11 electronic flow sensor (thermal differential type)

Model
Nature of the Manufacturer
Other
Product Category
Flow Switch
Place of Origin
City, Province
Overview
Illustrate:CX-FS-FR11 electronic flow sensor (thermal differential type) can be uesd to control flow.
Product Details

 CX-FS-FR11 Electronic flow sensor (Thermal differential type)
 

Brief Introduction
1.Suitable for the gas and liquid measurement
2.The set range can be 1-20m/s and have relay output (230VAC.4A).
3.Concise and direct indicator ,and with high reliable
4.Widely used in pneumatic and hydraulic systems, flow monitoring for recycled water, cutting fluid and lubricating oil , the protection of pump’s run idle
 
Main Features
1.No movable parts
2.Maintenance free and Easy installation
3.Suitable for variable diameter demand
4.Switching  value can be adjusted continuously
5.Extremely low pressure loss
6.Compact structure
7.LED indicator display flow trend and switch state
 
Technical parameters
Set range1…150cm/s( water),3…300cm/s(oil),20…2000cm/s(air)
OutputPNP, NPN, Relay ,4-20mA, NO+NC (SPDT)
Power supply24V±20%DC or 230V±15%AC
Switching CurrentMax.400mA(PNP or NPN type ), Max.4A( Relay type )
Unload currentMax.80mA
Flow indicatorLED (6)
Set typepotentiometer set
Proof Pressure range100bar
Temperature gradient4℃/s
Response time1--13s,standard is 2s
Initialization time8s
Electrical protectionreversed-phase ,short circuit ,overload protection
Protection classIP67
Medium temperature20--80℃
Environment temperature-20--80℃
Storage temperature-20--100℃
Connection M12 connector /2m cable (option)
MaterialProbe is stainless steel . Housing is PBT
Weight0.4kg
           
Model
ModelConnection Power Output
CX-FS-FR11-G12H-DA-QG1/2DC24V4-20mA
CX-FS-FR11-G12H-DC-RQG1/2DC24VRelay
CX-FS-FR11-G12H-WC-RCG1/2AC220VRelay
 
 Dimension .
 

G1/4 ScrewG1/2 ScrewSwitch outputAnalog output

Installation
 
When mounted vertically , it should install on the tube which flow direction is from the bottom to the top . When mounted horizontally , the probe should avoid air and sediment .

Electric connection 
 
 
LED functions and setup ( switch type )
Red LED light: If the cutting flow or velocity is less than the set value. The switch will be release and the analog value will be 4mA .
Yellow LED light: If velocity equal to the set value ,switch action .
Yellow and green LED light :It means that velocity is larger than set value. If the velocity will be faster ,the green LED  will be lighter ,
 

Installed the flow switch well ,let the velocity suit for monitoring and adjust the potentiometer .Let the first the green LEC just turn light . Then, after the velocity less than the current value , the switch will be released . To make the switch point less than the current velocity , it can adjust the potentiometer and make the green LED lighter .
LED function and setup ( analog output type ) 
Analog output type flow sensor , the output is 4-20Ma . It is proportional to the velocity ,the output belong to nonlinear . There are two knobs for each sensor , one is upper (20Ma) and ther other is (4Ma ) ,which used to output setup . 
Red LED light : The flow range is less than the lower limit . Output <4Ma 
Green LED light : The flow range is in the set range . 4mA
 
Installed the flow sensor well ,let the velocity suit for monitoring but with lower velocity ,adjust the lower knob and let the first green LED light (4Ma) . Let the velocity suit for monitoring but with upper velocity ,adjust the upper knob and let the fifth green LED light (20Ma) . Since then , the output is proportional to the velocity between upper and lower velocity ; It means that 4Ma corresponds to lower velocity and 20mA corresponds to upper velocity .