XMT*-808 series INTELLIGENCE TEMPERATURE CONTROLLER
OPERATION MANUAL
Ⅰ、Survey
XMT*808 series intelligence temperature controller uses nowadays the most advanced monolithic microcomputer as mainframe,reduce peripheral assembly,and improve the reliability;It adopts the control method of vague theory combined with traditional PID control, and make the control process with the advantage of rapid response、small overshoot、high steady state precision. It is intelligence temperature controller with the function of high performance、high reliability、complete input,its function is suitable to all the occasion needed temperature measurement and control,also be compatible with other industrial parameter measurement and control.
It adopts modular structure,further improve overall performance;The meter is operated with 4-keys,dual row 4-LED display for displaying the measurement value and set value or measurement value and output value, with manual /automatic switch and setting itself function;with characteristic of small volume、low power consumption、convenient operation、steady and reliable of running;They are now widely used for the automatic control system over the area of machinery, chemical, ceramics, light industry, metallurgy, petrifaction, heat treatment industry.
Ⅱ、Technical standard
2.1、Input and range(one meter can be compatible):
① Thermocouple:K(-50~1300℃)、S(-50~+1700℃)、T(-200~+350℃)、E(0~800℃)、J(0~1000℃)、B(0~1800℃)、N(0~1300℃)、WRe(0~2300℃)
② Thermal resistancer:CU50(-50~150℃)、PT100(-20~600℃);
③ Linearity voltage:0~5V、1~5V、0~1V、0~100mV、0~20mV;
④ Linearity current(with diffluent resistance):0~10mA、0~20mA、4~20mA
⑤ Linearity input: -1999~+9999 (user freely setting)2.2、precision:
① Input by thermal resistance , linearity voltage and linearity current 0.5F·S+1
② Thermocouple input adopt copper resistance or freezing compensate cold end 0.5 F·S +1;
③ Although the meter can measure B、S、WRE during the temperature 0~600℃,its measurement could not reach 0.5 class;
④ differentiate rate:1、0.1;
2.3、response time: ≤0.5s (filter parameter sets 0)
2.4、Adjusting mode:
① ON/OFF control method(Return difference can be adjusted);
② Common PID control(with the parameter of self-setting function)
③ Intelligence adjustment(including vague PID adjustment and advanced control algorithm with the parameter of self-setting function);
2.5、Output specification:it make out directly output parameter modularity or without modularity:
① The switch of relay contact point output(open+ closed):250VAC/7A or 30VDC/10A;
② SSR voltage:12VDC/30mA(apply for driving SSR relay);
③ Contact point output with controllable silicon: can contact 5~500A two directions controllable silicon;2 separate directions controllable silicon opposite direction parallel.
④ Liner electric current output: initial current and terminal current value can be defined when the output is 0~24mA(voltage range 11~23VDC);
2.6、Communication:Support RS485communication mode,adopt AIBUS communication agreement,and baud rate support the below selection :1200bps、4800bps、7200bps、9600bps
2.7、Alarm:Support two passive contact output,relay contact 250VAC/7A;It has four methods including upper limit, lower limit, positive deviation ,negative deviation .It can output 2 ways at most;
2.8、Tolerance for pressure when it is segregated:Between electric power ,relay’s contact and signal’s end ,do 2000V pressure tolerance test 1s,there is no abnormal phenomenon;
2.9、Movement with hand: Automatic /Manual;
2.10、Power supply:
① 85V-242VAC,50-60HZ;power consumption ≤4W
② 24VDC/AC power consumption≤4W ;
③ 220VAC±10% 50HZ;power consumption≤4W
2.11、working circumstance :
Environment temperature:0~50℃,humidity ≤85%,no corrode and strong electromagnetism disturb;
2.12、Product authentication:XMT*-808 series temperature meter acquire CE authentication and ROHS Environmental Protection authentication.
Ⅲ、Model selection
3.2 Product code
XMT □ 8 □ 8 □□
(1) (2) (3) (4) (5)
(1) The External dimension:
Blank:160×80×120 Installation hole 152×76;
A:96×96×110 Installation hole 92×92;
D:72×72×110 Installation hole 68×68;
E: 48×96×110 Installation hole 44×92;
F:96×48×110 Installation hole 92×44;
S:80×160×120 Installation hole 76×156
G:48×48×110 Installation hole 44×44
(2) Control Mode:‘8’:four key set, two row LED display,,fuzzy control.
(3) Additional alarm:‘0’:no alarm ; ‘1’:one group alarm;
‘3’:two group alarms ‘5’:voice alarm
(4) Signal input type:‘8’:freely exchange signal
(5) Suffix:
Main control output method:
‘Blank’:relay’s open and closed contact output;
‘A’:Single-phase over-zero spark pulse;
‘A3’:Three-phase over-zero spark pulse;
‘B’:Single-phase shift-phase spark pulse;
‘B3’:Three-phase shift-phase spark pulse;
‘C’:0~10mA or 4~20mA constant electric current output
‘E’:Linearity voltage output;
‘G’:ON/OFF solid state relay(SSR)adjustment output;
Auxiliary ways:
‘K’:with RS485 or RS232 communication module interface;
‘Wt’:with micro-printer output signal;
‘V’:DC24V、DC12V、DC5V output;‘P’:30 segment program
Ⅳ、Panel Explanation
4.1 Panel chart
4.2 Panel explanation
1、PV——- Measured value indicator (red)
2、SV——- Set value indicator (green)
3、A-M——– manual indicator lamp or setting itself(green)
4、ALM1—— AL1 indicator(red)
5、ALM2—— AL2 indicator(red)
6、OUT——–output indicator(green)
7、 SET——–function key
8、◄———– data automatic/manual shift function key
9、▼——-Data reduce key
10、▲——-Data addend key
Ⅴ、function and setting
5.1 Operation flow chart
Ⅵ、Fault Analysis and Clearance
XMT*808 series adopt advanced production process, and have the strict test before leaving factory, it improve the reliability of the meter .The usual fault caused by the wrong operation or parameter setting .If you find the fault couldn’t be cope with, please record it,and contact with the agent or us. Sheet 6-1 is the usual fault of XMT*808 series in the daily application:
Sheet 6-1 Common fault handling
fault symptom | analysis of causes | Disposal measurement |
Abnormal power(blank screen) | 1、poor contact of power cord 2、power switch without lose | Check the power |
Signal display do not correlate with the facts.(display “orAL") | 1、Wrong setting of input specification(Sn)2、Wrong signal connection. 3、Sensor break down 4、Input measurement signal exceed range | 1、check input specification2、check signal wire 3、check the sensor 4、check input signal |
Abnormal alarm output | 1、incorrect alarm defination parameter setting | 1、set alarm definition parameter value again. |
Abnormal PID output | Incorrect PID parameter setting,such as proportion、integral、differential parameter and so on. | Turn on setting itself again |
Attached1:Statement of meter’s parameter attention letter and English letter FAQ
1.What are your prices?
Our prices are subject to change depending on supply and other market factors. We will send you an updated price list after your company contact us for further information.
2.Do you have a minimum order quantity?
Yes, we require all international orders to have an ongoing minimum order quantity. If you are looking to resell but in much smaller quantities, we recommend you check out our website.
3.Can you supply the relevant documentation?
Yes, we can provide most documentation including Certificates of Analysis / Conformance; Insurance; Origin, and other export documents where required.
4.What is the average lead time?
For samples, the lead time is about 7 days. For mass production, the lead time is 20-30 days after receiving the deposit payment. The lead times become effective when (1) we have received your deposit, and (2) we have your final approval for your products. If our lead times do not work with your deadline, please go over your requirements with your sale. In all cases we will try to accommodate your needs. In most cases we are able to do so.
5.What kinds of payment methods do you accept?
You can make the payment to our bank account or PayPal