Short Description:Ⅰ.General introduction First of all thank you for using our meter, This manual contains instructions for the installation of meters, operations, parameter setting in the PC. Safety fence is a new type of meter that our Company recently developed, using photoelectric isolation technology, SMT ma...
Product Details

Ⅰ.General introduction

First of all thank you for using our meter, This manual contains instructions for the installation of meters, operations, parameter setting in the PC.

Safety fence is a new type of meter that our Company recently developed, using photoelectric isolation technology, SMT manufacturing process and international standards DIN Rail installation, and have a wide voltage, small size, long life, easy-to-install, and strong anti-interference, and other advantages. Instrumentation is for a group of signal input, two groups simultaneous signal output, communication using ModBus agreement, through RS-485 interface with the PC or PLC-controlled part on-line to concentrate on monitoring and control meters, in connection with the PC Meter can amend the parameters through PC.

Ⅱ. Technical Index

1、Input type: CU50、PT100、K、E、J、T、S、R、WR25、N、F2、0-5V、1-5V

2、Output precision : ±0.5%F.S

3、Output signal: two group 4~20mA(adjustable through parameter OUTH、OUTL)

4、Overall dimension(mm):106×76×25

5、Power supply:AC/DC 24~36V

6、Working circumstance:temperature 0~50℃,humidity﹤85%RH without.

corrode and strong electromagnetism disturb.

Ⅲ. Size appearance and meter connection scheme(consult)

0

Ⅳ. Code setting mode

Series code Name RemarkSetting rangeEx-Factory
1 PbSensor erroramendmentThe sensor have deviation can use itemto revisal0~±20.0 0.0
2FILTFilt modulusThe first order lag filter coefficient, the value is greater, the performance anti-jamming moment is stronger, but the response time lag. The pressure and flow control of its value should be smaller, temperature and level control should be relatively large0~5020
3OUTHAllow exportsmax valueRestrain maximum value of adjust output.outL~22002000
4OUTLAllow exports min valueRestrain minimum value of adjust output0~outH400
5LocKCode lock0-all the parameter can be revised1-only the SP can be revised0~500
 

6

 

Sn

 

Input type

‘0’Cu50 –50.0~150.0℃; ‘1’Pt100 –199.9~200.0℃;‘2’Pt100 –199.9~600.0℃; ‘3’K -30.0~1300℃;‘4’E -30.0~700.0℃ ; ‘5’ J -30.0~900.0℃;

‘6’T -199.9~400.0℃; ‘7’ S -30~1600℃;

‘8’ R -30.0~1700.0℃; ‘9’ WR25 -30.0~2300.0℃;

‘10’ N -30.0~1200.0℃; ‘11’ Idiosyncratic type ;

‘12’ 0~5V(0~10mA); ‘13’ 1~5V(4~20mA)

 

0~13

 

random

7 P-SHDisplay the high limitP-SH decide the display range, the value and unit are decided by factory and client freely.P-SL~9999random
8P-SLDisplay the low limitP-SL decide the display range, the value and unit are decided by factory and client freely.-1999~P-SHrandom
9AddrCommunication addresThe meter’s number in the control system0~630
10BAudCommunication baud rate‘0’1200;‘1’2400; ‘2’4800; ‘3’96000~39600

When the meter connect the PC hrough the RS-485, it can amend meter parameters through the PC, parameters order please refer to Table 4-1. The default address for its communications “0″, the baud rate for “9600″. To connect multiple meters, the PC software address amend for “0″, baud rate changed to “9600″, at this time connecting on a meter, the menu address parameters will be changed to other numerical parameters (not larger than 63), after editing and then another meter to amend the address. Each meter is the only address, can not be repeated. And so on until the end of amending the connecting instrument.Ⅴ.Meter communications and parameters amending

Note: When the meter amended the address, the address numerical value labeled best on the meter avoiding confusion. PC software use refers to the help function in PC software.

4~20mA or 0~10mA linearity current input can achieve by changing 250Ω or 500Ωresistance to 1~5V or 0~5V voltage signal,and then input from A2、28 terminal.

Ⅵ. Fault Analysis and Clearance

Safety fence adopt advanced production process, and have the strict test before leaving factory, it improve the reliability of the meter .The usual fault caused by the wrong operation or parameter setting .If you find the fault couldn’t be cope with, please record it,and contact with the agent or us. Sheet 6-1 is the usual fault of Safety fence in the daily application:

Sheet 6-1 Common fault handling

fault symptomanalysis of causesDisposal measurement
Abnormal power1、Poor contact of power cord

2、Power switch without lose

Check the power
PC display do not correlate with the facts.(display‘FF’)1、Sensor model mismatch

2、Wrong signal connection

1、Check sensor model and meter interior input parameter 2、check signal wire

3、Check communication wire

Abnormal output1、Wrong connecting output wire1、Check output connection

2、Check parameter OUTH、OUTL