Welcome Customer !

Membership

YIFANG ELECTRIC GROUP INC.
Free Member ·1YRS
ZhengZhou,HeNan
Manufacturer

Main Products: Power Cable|Bare Wire|Control Cable

Xwboo>Products

0.6/1kv Cu/XLPE/SWA/PVC Power Cable

Model
Nature of the Manufacturer
Manufacturer
Product Category
Power Cable up to 1kV
Place of Origin
City, Province
Overview
0.6/1kv Cu/XLPE/SWA/PVC Power Cable
Product Details

Brief

XLPE insulation power cable has a number of advantages over paper insulated and PVC insulated cable. XLPE cable has high electric shength, mechanical shength, high-aging resisting, environmental stress resisiting anti-chemical corrossion, and simple construction, using convenient and higher operating of long term temperature. It can be laid with no drop restriction.

Various of flame-retardant and non-flame retardant XLPE cable can be manufactured with three technology (peroxide, silance and irradiation crossing-linking). The flame-retardant cable covers all kinds of low-smoke, low-halogen, low-smoke halogen free, and non-smoke non-halogennated and three classes of A, B, C.

Our XLPE cable can be manufactured accoding to company’s specification which is equivalent to IEC 60502, IEC 60332, IEC 60754. Sone indexes are superior to above international standard.

Some of special XLPE cable can be manufactured according to the other standard required by customers.

Scope

TypeNo. of CoreNominal Cross-section of conductor mm2
Cu(Al)/XLPE/PVC(PE)

Cu(Al)/XLPE/ATA/PVC(PE)

Cu(Al)/XLPE/AWAPVC(PE)

11.5-1000
Cu(Al)/XLPE/STA/PVC(PE)
Cu(Al)/XLPE/SWA/PVC(PE)
2, 3, 4, 51.5-400
3+1, 4+1, 3+22.5-400

Main technical

1) D.C .Resistance: Conductor resistance of finished cable per kilomerer at 20oC is not more than the following:

Nominal Cross-section mm2152.546101625
Cu core12.17.414.613.081.831.150.727
Al core18.112.17.414.613.081.911.20
Nominal Cross-section mm235507095120150185
Cu core0.5240.3870.2680.1930.1530.1240.0991
Al core0.8680.6410.4430.3200.2530.2060.164
Nominal Cross-section mm22403004005006308001000
Cu core0.07540.06010.04700.03660.02830.02210.0176
Al core0.1250.1000.07780.06050.04690.03670.0291

Voltage Test

Each drum of finished cable should withstand power frequency voltage 3.5kv for 5 miniutes, the insulation is not breakdown.

Service conditions

The cable is applied to fixed insulation for rated voltage 0.6/1kv of power transportation and distribution line.

Max. rated temperature of conductor nominal operating 90oC.

Short circuit: max. for 5 sec. 250oC.

The cable can be laid without drop retriction, and the environment temperature shall not be lower than 0oC