D.C Resistance of finished cable at 20℃ per km is not more than the following:
| Nominal cross-section mm2 | 15 | 2.5 | 4 | 6 | 10 | 16 | 25 |
| Cu core | 12.1 | 7.41 | 4.61 | 3.08 | 1.83 | 1.15 | 0.727 |
| Al core | 18.1 | 12.1 | 7.41 | 4.61 | 3.08 | 1.91 | 1.20 |
| Nominal cross-section mm2 | 35 | 50 | 70 | 95 | 120 | 150 | 185 |
| Cu core | 0.524 | 0.387 | 0.268 | 0.193 | 0.153 | 0.124 | 0.0991 |
| Al core | 0.868 | 0.641 | 0.443 | 0.320 | 0.253 | 0.206 | 0.164 |
| Nominal cross-section mm2 | 240 | 300 | 400 | 500 | 630 | 800 | 1000 |
| Cu core | 0.0754 | 0.0601 | 0.0470 | 0.0366 | 0.0283 | 0.0221 | 0.0176 |
| Al core | 0.125 | 0.100 | 0.0778 | 0.0605 | 0.0469 | 0.0367 | 0.0291 |
Voltage test:
Each drum of finished cable should withstand power frequency voltage 3.5kV for 5 minutes,the insulation is not breakdown.
Service conditions and operation parameters of Cable:
The cable is applied to fixed installation for rated voltage 0.6/1kV of power transportation and distribution line.
Max. rated temperature of conductor. nominal operating 90℃
Short circuit: max. for 5 sec.250℃
The cable can be laid without drop restriction, and the environment temperature shall not be lower than 0℃.