Application
The assembled insulated conductor shall be suitable for use in a system having a standard operating voltage not exceeding 600/1000V. The cores of an aerial bundled conductor shall be laid-up with a left-hand lay. The length of lay shall be 55-75 times the diameter of a phase conductor.
Construction
The conductors shall be stranded circular and ,except where otherwise stated,shall comply with all the requirement for class 2 compacted stranded circular conductors of SANS 1411-1.
Specification
(1)Self-supporting
Phase | Phase | Phase | Approx.Overall Diameter | Min.Bending Radius | Max. D.C. Resistance of Conductor at 20℃ |
AAC+UV-XLPE | Compact Conductor | UV-XLPE Insulation |
No.X Normal Cross Section of Cores | No.of Al Wires | Overall Diameter | Thickness | Min. | Diameter |
No. X mm2 | - | mm | mm | mm | mm | mm | kN | ohm/km |
4 X 16 | 7 | 4.8 | 1.2 | 0.98 | 7.2 | 17.42 | 2.07 | 1.91 |
4 X 25 | 7 | 6.0 | 1.4 | 1.16 | 8.8 | 21.3 | 3.3 | 1.2 |
4 X 35 | 7 | 7.0 | 1.6 | 1.34 | 10.2 | 24.68 | 4.5 | 0.868 |
4 X 50 | 7 | 8.3 | 1.6 | 1.34 | 11.5 | 27.83 | 6.2 | 0.641 |
4 X 70 | 19 | 10.0 | 1.8 | 1.52 | 13.6 | 32.91 | 8.9 | 0.443 |
4 X 95 | 19 | 11.6 | 1.8 | 1.52 | 15.2 | 36.78 | 12.3 | 0.32 |
4 X 120 | 19 | 13.0 | 1.8 | 1.52 | 16.6 | 40.17 | 15.6 | 0.253 |
4 X 150 | 19 | 14.6 | 1.8 | 1.52 | 18.2 | 44.04 | 19.2 | 0.206 |
3 X 16 | 7 | 4.8 | 1.2 | 0.98 | 7.2 | 15.55 | 2.07 | 1.91 |
3 X 25 | 7 | 6.0 | 1.4 | 1.16 | 8.8 | 19.01 | 3.3 | 1.2 |
3 X 35 | 7 | 7.0 | 1.6 | 1.34 | 10.2 | 22.03 | 4.5 | 0.868 |
3 X 50 | 7 | 8.3 | 1.6 | 1.34 | 11.5 | 24.84 | 6.2 | 0.641 |
3 X 70 | 19 | 10.0 | 1.8 | 1.52 | 13.6 | 29.38 | 8.9 | 0.443 |
3 X 95 | 19 | 11.6 | 1.8 | 1.52 | 15.2 | 32.83 | 12.3 | 0.32 |