HMCXZ AC Resonant Test System is suitable for 10KV, 35KV, 110KV, 220KV, 500KV polyhexene power cable AC withstand voltage test. It is suitable for the AC withstand voltage test of large-capacity equipment such as 60KV, 220KV, 500KV GIS, transformers, insulators, busbars, busbars, and hydroelectric generators.
HMCXZ AC Resonant Test System is mainly composed of variable frequency controller, excitation transformer, high voltage reactor, high voltage divider and so on. The frequency conversion controller is divided into two categories, 55KW and above are desktop type, and below 55KW is portable box type; it is composed of a controller and a filter. The main function of the variable frequency controller is to convert the 380V or 220V power frequency sine alternating current with fixed amplitude and frequency into a sine wave with adjustable amplitude and frequency. And provide power for the whole set of equipment. The function of the excitation transformer is to raise the output voltage of the variable frequency power supply to a suitable test voltage. The high voltage reactor L is an important part of the resonant circuit. When the power frequency is equal to 1/(2π√LCX), it will resonate in series with the tested product CX.
The AC Resonant Test System is to change the system inductance and test frequency to make circuit in resonant condition. Its electric circuit is shown in Fig.1. The adoption of variable frequency resonant technology reduces the capacity of power source and the weight of equipment, which facilitates on-site test.
Fig.1
Hot tag: series resonance test set,ac dielectric test system supplier,resonance hipot test device,cable withstand voltage test device manufacturer.
4000kvA/800kV Variable Frequency Resonant test set applied test object
Device combine Test object
Reactor: 1000kVA/200kV 4 pcs
Exciting transformeroutput selection
110kV,630mm2,3km power cable
4 pcs in parallel
6kV
220kV,630mm2,1.2km power cable
4pcs,2 in series, 2group in parallel
12kV
110 kV power system、busbar、GIS,etc
2 pcs in series
12kv
220 kV power system、busbar、GIS,etc
3 pcs in series
12kv
500 kVpower system、busbar、GIS,etc
4 pcs in series
36kv
Test object & Test requirement
1) .500KV and below switche and instrument transformer AC withstand voltage test,test frequency 30-300Hz,test voltage 740kV,test time 1min.
2.220kV/630mm2 0.6km cable AC withstand voltage test,capacitance≤0.086uF,test frequency 30-300Hz,test voltage 216kV,test time60min.
3.110kV/630mm2 1.5Km cable AC withstand voltage test,capacitance≤0.3uF,test frequency 30-300Hz,test voltage 128kV,test time 60min.
Product main parameter
Item
Configuration
Main parameter
Quantity
1
High voltage reactor
JLB-200kVA/6kV12kV/36kV/0.2kV/0.4kV
1set
2
Variable-frequency power source
CHXB-F-200kW/0.22/kV/0.38kV
1 set
3
High voltage reactor
DK-1000kVA/200kV
4 sets
4
High voltage reactor
FCR-800kV/750pF
1 set
5
Testing cable
1 set
6
Insulating support
1set
All Specifications can be customized according to client’s requirements.
2.when withstand, Reactor selection Instrunction
1)the above configuration proposal is made according to the longest cable.
2) for short cable or test object with no capacitance,in order to reach to find resonance frequency,usually connect the resonance capacitor with loop in parallel.
4000kvA/800kV Variable Frequency Resonant factory release test picture
Reference date of equivalent capacitances of common testing object of AC resonant test system
C=εΑ/d ,ε---permittivity of medium,Α---electrode area,d---Electrode distance Appendix 1. List of electricity capacity of several common subjects
Testing object
Capacitance
Power transformer 1-100MVA
1-6MVA:3000-10000pF
10MVA:5000-12000 pF
20MVA:7500-15000 pF
60MVA:13000-20000 pF
100MVA:15000 Pf-20000 pF
300MVA:20000 Pf-30000 pF
CVT
3000-5000 pF
HV circuit breaker、CT、PT
100-1000 pF
Swichgear(common and SF6)
300-1000 pF
high-pressure pipe
50-600 pF
Insulator
<100 pF
Insulation tool
10-100 pF
overhead conductor and bus(per meter)
8-10 pF
Appendix 2:35KV And 35kV below capacitance of cable
Cross-sectional area of the single conductor (mm²;)
18/20KV
6/6KV 6/10KV
8.7/10KV 8.7/15KV
26/35KV
μF/KM
μF/KM
μF/KM
μF/KM
25
0.1163
0.1922
0.1567
0.0992
35
0.1251
0.2116
0.1725
0.1061
50
0.1362
0.2357
0.1917
0.1150
70
0.1508
0.2693
0.2167
0.1263
95
0.1643
0.2999
0.2400
0.1368
120
0.1760
0.3266
0.2603
0.1460
150
0.1893
0.3570
0.2834
0.1563
185
0.2026
0.3873
0.3123
0.1665
240
0.2207
0.4296
0.3439
0.1805
300
0.2387
0.4706
0.3755
0.1945
400
0.2648
0.5311
0.4213
0.2146
500
0.2876
0.5839
0.4613
0.2321
630
0.3151
0.6481
0.5099
0.2533
Appendix 3:110KV、220KV capacitance of cable
110KV
220KV
Cross-sectional area of the single conductor(mm²;)
Capacitance(μF/KM)
Cross-sectional area of the single conductor(mm²;)
Capacitance(μF/KM)
240
0.136
240
0.110
300
0.147
300
0.117
400
0.165
400
0.125
500
0.182
500
0.134
630
0.201
630
0.144
800
0.224
800
0.155
1000
0.265
1000
0.180
1200
0.282
1200
0.190
1400
0.198
1600
0.204
1800
0.212
2000
0.222
attention
prevent fire or personal injury!
Use appropriate power cord: can only use this product special, and conform to the product specifications of the power cord.
Properly connect and disconnect: when tests conductors and charged terminal connections, not optional connect or disconnect test wires.
Product grounding: this product except through the power grounding wires grounding,shell grounding column must be grounded. In order to prevent the shock, grounding must be connected with the ground conductor. With this product in the input or output terminal connections and shall ensure the product before already correct grounded.
Note that all terminal's rated value: in order to prevent fire or shock, please note all the rated value and mark of the product. please read this product before operation instruction, in order to further understand the information about rated value.
Don't operate without instruments cover plat ,such as already unloaded plat or panel, please do not operate this product.
In a suspicious fault, not operation: such as suspect this product has damaged, please contact the company maintenance personnel for inspection, do not continue to operate.
FAQ
1.Can you provide the training for us?
Yes, we can provide free training for our client at our factory.
If you require the training on-site, we also can arrange accordingly.
We have 10 seasoned engineers who become our technical team, they flied many countries for client’s installation and commissioning!
2.What is your after-sale service
We have 10 seasoned technical engineer as the after-sale service team.it is lead by our duty manager. We promise that our engineer can give answers within 1 hour and deal with equipment failure within 24 hours in time.
3.What’s the warranty period ?
Our warranty period is one year .
The product can be replaced within 1 month, can be repaired for free charge for one year and maintenance for lifetime.
What is more, our warranty can be extended only charged small warranty fee.