This transformer loss and no-load loss tester is mainly used for the measurement of the transformer capacity and other characteristic parameters, such as transformer type, no-load current, no-load loss, load loss, impedance voltage and so on.
Product Details
HM5003 Transformer No-load tester
Brief Introduction
This transformer loss and no-load loss tester is mainly used for the measurement of the transformer capacity and other characteristic parameters, such as transformer type, no-load current, no-load loss, load loss, impedance voltage and so on.
Function
1.It can measure a variety of distribution transformer, power transformer capacity instead of the additional extra power. It is more convenient and efficient.
2.Combined with the external power source, voltage, current regulator equipment etc, it can measures various transformer parameter such as no-load current, no-load loss, impedance voltage, load loss and so on.
3.Characteristic test of transformer, test range is wide,flexible configured.only through the simple connection to current transformer and voltage transformer, test scope can be enlarged to high-grade power transformer.
4.Short-circuit the terminals of cable,humanization design,with lock,easy connected to fasten units of transformation.
5.All results are automatically carried out relevant correction. You only need to input the related parameters (such as temperature, load adjustment coefficients etc), then the instrument can automatically calibrate such as waveform deformity correction, temperature correction, correction of non rated voltage, rated current correction,so that the accurate is much higher
6.The maximum voltage is up to 750V and the maximum current is up to 100A range with protection circuit in it,when you make the characteristic test of transformer.don’t worry the precision and damage of the instrument due to in-proper shift.
7.The voltage and current range can be very flexible and easy to expand by connecting the external CT or VT
8.It has large screen, high brightness LCD display, English menu and operation tips, friendly man-machine interface and wide temperature tolerance, brightness adjustable type LCD screen, which can adapt to the different temperature.
9.Thermal sensitive printer is set inside the instrument,it can easily print on site.
Hot tags: Transformer capacity tester ,transformer capacity & loss tester,short circuit test of transformer
Technical Parameters
1.The output range of built-in battery
Voltage:0~10V
Current:0~10A
2. The input range of characteristic test power source
Voltage:0~750V
Current:0~100A
3. Accurate of test
Voltage, current:±0.2%
Power:±0.5%(CosΦ>0.1), ±1.0%(0.02
4. Working temperature
-20℃~+60℃
Packing List
No.
Name
Picture
Quantity
Remark
1
Host
1pc
2
Test cable
1set
Yellow , green and red
3
Short-circuit cable
1pc
4
Charger
2pc
5
USB data cable
1pc
6
Earth cable
1pc
7
Print paper and
1pc
8
Instructions
--
9
Inspection Report
--
Factory release test about HM5003 Transformer No-load tester
Service and Support
1.Factory Release Test
Products are operated in correct way strictly according to production process.
About qualified product, inspector will issue factory test report and certification of quality.
Sub-quality products are prohibitted to leave factory.
2.Hand-over Technical Documents
Wuhan Goldhome Hipot Electrical Co.,ltd will afford Operation Manual, Packing List, Cerficiation of quality while in prdoucts acceptance.
3.Technical Guidance
After delivering device customers,Wuhan Goldhome Hipot Electrical Co.,ltd can provide systematic technical training, to ensure operator know the operation produce maintenance and trouble-shooting , and able to make test on site.
After-sale Service
1.First Time Use guidance
For the first time use, technical staff will guide customer how to make testing at site.
2.Three-years Warranty
The warranty period of all equipment is three years, lifetime maintenance.
During warranty period, free maintenance or replacement are provided timely for any quality problem . Finally we will afford customer a satisfactory solution, whether repair , replace or return it back.
3.Trouble-shooting
fault that users can solve by themselves, we guarantee to give timely telephone guidance and bear the necessary cost.
If meet any fault not impossible to be solved by end-user, we will afford the best solution within 24 hours . Produce will be repaired within 10 days and delivery back to customer.
More related products
Company profile
Wuhan Goldhome Hipot Electrical Co.,ltd is one of the earliest enterprises specially in develop, design and manufacture high-voltage testing equipment in China. .The company advantage products inlcuded AC Resonant Test System, GID PD Free Test System, AC/DC Hipot Tester, Primary Current Injection, Multi-frequency inductive withstand voltage test system, VLF Hipot Tester, etc.
Goldhome Hipot will always stick to the leading science and technology, quality first, heart-to-heart business and win-win cooperation!