4.Input voltage:0~600V/ Three phase (combination of 3 sets single phase )5.Input current:0~80.5A6.Rated capacity :48.3kVA*3 7.Output voltage:0.46~12V phase voltage, 0.26~6.9V line voltage(open) 8.Output current :100~7000A
Product Details
7000A Long time running primary current test set system
Summary
Primary Current Injection Test Set is a necessary equipment in various industries that require high current in electrical commissioning. It is used in power plants, transformer and distribution stations, electrical manufacturing plants and scientific research and laboratory units. It belongs to the short-term or intermittent working system. The HMSLQ Primary Current Injection Test Set produced by our company has the characteristics of stable performance and convenient use and easy maintenance.
Structure
This product accepts the split structure, it is made up of electric automatic console, inductive voltage regulator and Primary current generator. it connects with the tested object through the high current conduct wire which is through the primary current generator. Meanwhile, it measures, monitors and operates through the CT in the primary current generator and the current indicator, voltage indicator, different indicators and buttons of display screen in the console.
General view of the Primary Current Injection Test Set
(from left to right: automatic console, induction voltage regulator, primary current generator)
Main Technical Parameter
Electric inductive voltage regulator(3sets build in one cabinet)
Features:
The inductive voltage regulator adopts a carbon-free brush to isolate the induced output voltage
No corona no spark
It has heat conduction heat dissipation sheet which can be for long-time running working.
Parameter:
Input voltage:380V/single phase
Rated capacity :50kVA*3
Input current :131.5A
Output voltage:25~650V
Output current :76.9A
Running time:≤24hours
Cooling mode:oil-circulating cooling
Electric automatic console
Features:
1) The control screen accepts the IPC.
2) The sample signal panel is passive signal converter with multiple and Isolation Shield Protection. It can completely eliminate the destructive impact of high voltage breakdown square voltage and current on the control power supply.
3) Controller parameters can set to do the same batch when the power is off without needing resetting, permanent save!
4) Test result can save 50 records for recording and printing.
Parameter|:
Input voltage :380V/three phase
Input current :227.9A
Rated capacity :150kVA
Output current indicator :7000A three phase indication
Output voltage indicator:450V
Meter accuracy:Class 0.5
Over current setting :100~7000A(3 phase /single phase setting )
Current balance:Output current can be arbitrary adjustment in phase or single phase, three phase output in balance by intelligent electric automatic control
Over-current bounce release time:7mS
Timing range:0~999S、M、H Switchable
Running time:≤24 hours
Cooling mode :air blower cooling
Primary current generator
Features:
1)it accepts full-insulation structure, T3 copper lead wire, cold-rolled silicon steel plate.
2) The transformer use the double winding, low voltage input winding and high voltage output winding.
3) it installs the electrostatic shielding between the low voltage and high voltage, the low voltage and iron core.
4) Magnetic coupling between high voltage winding and low voltage winding, no electrical connection.
Parameter:
Input voltage:0~600V/ Three phase (combination of 3 sets single phase )
Input current:0~80.5A
Rated capacity :48.3kVA*3
Output voltage:0.46~12V phase voltage, 0.26~6.9V line voltage(open)
Output current :100~7000A
Current Transformer:HL1-10000A/5A(3pcs)
Accuracy of CT:Class 0.5
Running time:≤24 hours
Cooling mode:air blower cooling
Product Features:
1.Electric induction voltage regulator
1) No-contact magnetic induction isolation voltage regulating transformer
2) The output voltage can be regulated through mechanical drive using worm gear operated and step motor. It has the features of adjustable any parameter value and precise output.
2.Three phase primary current generator
1) It accepts full-insulation structure, T3 copper lead wire, cold-rolled silicon steel plate.
2) The transformer uses the double winding, low voltage input winding and high voltage output winding.
3) It installs the electrostatic shielding between the low voltage and high voltage, the low voltage and iron core.
4) Magnetic coupling between high voltage winding and low voltage winding, no electrical connection.
3. Electric automatic console
1)The control screen accepts the IPC.
2) The sample signal panel is passive signal converter with multiple and Isolation Shield Protection. It can completely eliminate the destructive impact of high voltage breakdown square voltage and current on the control power supply.
3) Controller parameters can set to do the same batch when the power is off without needing resetting, permanent save!
4) Test result can save 50 records for recording and printing.
5) 9 inch LCD touch screen display, PLC control, high speed thermal printer.
6) High precision sensor and high performance 14 bit AD acquisition chip.
7) Man-machine dialogue full keyboard operation mode, the whole process is intelligent.
8) Automatic up flow test and manual up flow test are optional, flexible and simple operation.
9) Real-time display output current, time results, with intuitive display.
10) Perfect over current protection, arbitrary setting is available for target output current value, current upper limit and current endurance time
11) The output current can be regulated and operated as three phase/single phase. and it also can automatically gain to make sure the three-phase output which can be in balance.
12) With the function of zero return detection, zero return can be determined before the test, safe and reliable
13) Approximation up current algorithm, automatic current endurance timing after reaching the set target output current, and the motor automatically returns to zero after the timing.
14) If the upper limit of output current is exceeded, the motor will automatically return to zero and give sound and light alarm.