Arrester Tester

Model
Nature of the Manufacturer
Manufacturer
Product Category
Arrester Tester
Place of Origin
City, Province
Overview
1.Measure range:voltage 0~30kV current:0~1000μA2.Accuracy:voltage 1%3.Environmental temperature:0~+40℃4.Relative humidity:25℃时≤85%5.Altitude:<1000M
Product Details
I.Brief introduction


HM6020 zinc oxide arrester tester is specially designed for detecting the internal defects of poor electrical contact between clearance zinc oxide arrester MOA valves used in power systems up to 10kV and below , to measure the leakage current of MOA at DC reference voltage (U1mA) and 0.75 U1mA .The instrument is composed of dc high voltage power supply, measurement and control system,and all components are concentrated in one case, in small size and light weight . It is an essential equipment for the field test of power system and zinc oxide arrester.

Hot tags : Lighting arrester tester , MOA tester , Lighting arrester test equipment

II.Technical parameter


1.Measure range:voltage 0~30kV current:0~1000μA

2.Accuracy:voltage 1%

3.Environmental temperature:0~+40℃

4.Relative humidity:25℃时≤85%

5.Altitude:<1000M

6.Power supply:220V±10%

7. Frequency:50±1HZ

details


III.How to use


1.Open the cover of the instrument case and firmly ground the instrument case.

2. Insert one end of the lightning arrester into the high pressure bushing of the instrument (H end), the other end is clamped with a wire clip. Or a special insulated wire is used to lead out the external connection test product from the high voltage end.

3. Close the power switch,after the internal self-inspection of the instrument, the alarm light is on and the discharge light is on. Press the test button, and the indicator value of the two watch heads is zero ±1 word.

4. Press the reset button, the alarm lamp will be off, and the instrument will enter the detection state for testing.

5.Press the test button for about 1 second and then release it. The instrument will automatically complete all the test items of MOA.

6.Attention

(1) If the detection button is pressed and the alarm light is on, it indicates that there is a defect of poor contact inside the MOA,or the external connection is weak.After the discharge lamp is on, check whether there is a problem with the external wiring, or press the reset button after replacing the sample for the next test.

(2) If the alarm light is not on, it indicates that the internal contact of MOA is good and there is no wiring problem,the instrument will automatically enter the status of measuring U1mA and Id, and the test results are displayed on the meter header. After the discharge lamp is on, the test is finished, remove the test wiring or replace the sample for the next test.