HM6000 gas leak monitor can be widely used in various voltage levels of SF6 opening and closing room, combined electrical room (GIS room), SF6 main transformer room, etc.
Product Details
Product description
HM6000 gas leak monitor can be widely used in various voltage levels of SF6 opening and closing room, combined electrical room (GIS room), SF6 main transformer room, etc. It mainly detects the SF6 gas content and oxygen content in the ambient air. If the gas content exceeds the standard or lack of oxygen, it can alarm in real time, and automatically turn on the ventilator for ventilation, and has many rich functions such as temperature and humidity detection, voice prompts for working status, remote alarm, historical data query, etc.
Features
1.Advanced technology: based on the principle of sound speed, high precision, long life and good stability.
2.Wide measurement range: quantitative/qualitative measurement display in a wide range of 0~30000ppm.
3.Intelligent correction: The system has an automatic correction function, which can effectively overcome the influence of environmental factors such as temperature and humidity.
4.Good compatibility:
4.1) Multi-channel switch, analog output, seamless integration with integrated automation system.
4.2) Optional wireless alarm function.
4.3) Optional toxic gas (such as CO, CH4, H2S) content monitoring.
4.4) Optional external input signal interface, input signal can come from smoke probe, door sensor switch, etc..
4.5) Optional output interface to realize many intelligent control functions such as automatic fire alarm, start/stop dehumidifier, and electric control door.
4.6) Optional digital SF6 density relay combined with networking to form a comprehensive SF6 gas leakage monitoring system.
4.7) Optional remote network to monitor the operating status of the system and directly control the operation of the host or transmitter.
Technical Parameters
SF6 measurement index
Measurement range
0~30000ppmv
Alarm point
Can be set within the measurement range,default 1000ppmv
Citation error
±5%FS
Repeatability error
<5%FS
Zero drift
<5%FS
Range drift
<5%FS
Oxygen measurement index
Detection concentration
0~25%
Oxygen concentration alarm point
18%
Oxygen measurement accuracy
<0.4%,O2at21%
Other indicators
Temperature measurement range
-25℃ ~ +99℃
Temperature detection accuracy
±0.5℃; Display accuracy:0.1℃
Humidity measurement range
0~99%RH
Humidity detection accuracy
±0.5%RH; Display accuracy:±0.1%RH
power
AC 165-260V 50Hz
Common troubleshooting
Lease refer to the following methods for troubleshooting in turn:
The system host has no display
1. Check whether there is power input;
2. Check whether the power switch of the host is turned on;
3. Open the mainframe junction box and check whether the power input socket is tight;
4. If no problems are found in the above inspections, please contact our technical support staff immediately.
The display of the host or display unit is chaotic or partly without display
1. Turn off the total power of the system and restart after 10 seconds
2. Check whether the connector of the collector is tight;
3. If no problems are found during the above inspections, please contact our technical support staff immediately.