MD0630T01A 6mA 30mA AC DC Sensitive Leakage Monitoring Device RCD Module Residual Current Sensor
Product Overview
IVY offers MD0630T01A for monitoring and/or providing shock protection and fault protection on AC and DC installations and for EV charging applications. MD0630T01A is a RCD sensor specifically developed for EV-charging providing all-current sensitivity. The sensor can issues an alarm signal in case of hazardous electrical faults (DC and AC). It has the characteristics of accurate measurement, small size and integration. The RCD sensor can be set separately for AC and DC leakage and has a digital output function.
MD0630T01A is an automotive grade leakage current sensor also called residual current monitoring (RCM), residual current detection (RCD), differential current sensor, leakage current detector and fault current sensor. Type A, B and B+, dedicated to detect to DC, AC and DC+AC leakage current measurement. The MD0630T01A can monitor DC (6mA) and AC (30mA) residual currents, it is connected in series with the AC supply to an EV and will provide a signal output if a DC current ≥ 6mA DC flows in the circuit. In addition, our delivery time is also guaranteed.
IVY RCD sensor is widely used for electro-medical instruments, ventilation systems, inverters, UPS, Electric vehicle charging stations, lifts, escalators, welding equipment, smart home, industrial machines, elevators, IOT, photovoltaic systems.

Product Features
1. Complies with the DC and AC protection requirements of IEC62752 or IEC62955
2. Small Size; Integration Design; Vertical(Pin, Pin&Cable Type)/Horizontal(Cable Type) Mounting Optional
3. Integrated self-monitoring and test functions; 3000A surge withstand capability
4. AC DC Leakage Data Readable; Alarm Value Programmable; 3 Way Alarm Outputs; Digital Output
5. URAT Comm, with Modbus Protocol; Standard: EN 61000-6-3:2007+A1, EN IEC 61000-6-1:2019
6. Certification: TUV(IEC62955/IEC62752/IEC61851-1/IEC62196); UL2231-1/UL2231-2; IS17017; CE-EMC
7. Type B RCD/RCM for EV Charger Protection; Electrical Safety at Low Cost (Compared to Type B RCCB)
8. Robust Mechanical and Electrical Design for Harsh Environmental Conditions

Product Parameters
Wide voltage input: 12V±20%
Measuring current range: DC current 2-15mA; AC current 3-100mA (default threshold: DC 6mA, AC 30mA)
Accuracy : at 25℃, DC±0,2mA, AC±0.3mA
Can read current value and set alarm current value
Three outputs: DC alarm, AC alarm, AC/DC alarm
Working environment temperature: -25℃~+80℃
Plastic case, small SIP package
Application-EV Charging Mode