MD0630T01A EV Charger Tester Leakage Detection RCD Type B 30mA AC 6mA DC Residual Current Sensor
Product Overview
MD0630T01A is a high sensititivity AC DC leakage current sensor. which can also be called residual current sensor, residual current monitor (RCM), residual current device(RCD), differential current sensor, leakage detection sensor, fault current sensor etc.
The AC/DC sensitive residual current monitoring module is suitable for fault current monitoring in charging stations where direct and/or alternating fault currents are likely to occur the value of which is constantly greater than zero.
The residual current monitoring device detects the residual current caused by leakage and residual currents in the conductors passed through the measuring current transformer.
The residual current monitoring module measures AC and DC currents and issues alarm signal when the DC component of the residual current reaches a preset value.
To satisfy new standards including IEC 62955 and IEC 60364-7-722, the charging of electrical vehicles requires residual current sensors to avoid hazardous situations in cases where the vehicle battery (DC) is connected to the home power supply (AC). Generally, AC/DC sensitive residual current sensors can be used where direct current and alternating current circuits are directly connected and therefore AC/DC leakage currents can occur.
By using a IVY RCD current sensor integrated into an IC-CPD or wall box, customers can save the high costs of installing a type B RCCB to provide all-current sensitivity and electrical safety at low cost.

Product Features
1. Complies with the DC and AC protection requirements of IEC62752 or IEC62955
2. Small Size; Integration Design; Vertical(Pin, Pin&Cable Type)/Horizontal(Cable Type) Mounting Optional
3. Integrated self-monitoring and test functions; 3000A surge withstand capability
4. AC DC Leakage Data Readable; Alarm Value Programmable; 3 Way Alarm Outputs; Digital Output
5. URAT Comm, with Modbus Protocol; Standard: EN 61000-6-3:2007+A1, EN IEC 61000-6-1:2019
6. Professional Certification: TUV(IEC62955/IEC62752/IEC61851-1/IEC62196); UL2231-1/UL2231-2; IS17017; CE-EMC
7. Type B RCD/RCM for EV Charger Protection; Electrical Safety at Low Cost (Compared to Type B RCCB)
8. Robust Mechanical and Electrical Design for Harsh Environmental Conditions

Product Parameters
Wide voltage input: 12V±20%
Measuring current range: DC current 2-15mA; AC current 3-100mA (default threshold: DC 6mA, AC 30mA)
Accuracy : at 25℃, DC±0,2mA, AC±0.3mA
Can read current value and set alarm current value
Three outputs: DC alarm, AC alarm, AC/DC alarm
Working environment temperature: -25℃~+80℃
Plastic case, small SIP package
Typical Application
Appliance ground fault detection
Solar inverter residual current
Converter leakage current detection
UPS and other power ground fault detection
Electric vehicle charging station
Single or 3 Phases differential current detection