Welcome Customer !

Membership

Zhejiang THOR Electric Co., Ltd.
Free Member ·1YRS
WenZhou,ZheJiang
Manufacturer

Main Products: Surge Protective Device|Surge Protector

Xwboo>Products

Zhejiang THOR Electric Co., Ltd.Free·1YRS

  • E-mail

    info@thorspd.com

  • Phone

    860577-62677705

  • Address

    Wenzhou Economic Development Zone, Zhejiang Province,China

Contact Now

TRSS-485 Control Signal Surge Protectors

Model
Nature of the Manufacturer
Manufacturer
Product Category
Signal Surge Protection
Place of Origin
City, Province
Overview
TRSS-485 Control Signal Surge Protectors
Product Details


Product introduction:
The TRSS control signal lightning protector is used to protect sensitive high-spee communication network lines from damage caused by lightning induced voltage, power interference, electrostatic discharge, etc. The signal lightning protection device adopts multi-level protection circuit, selects world-famous components, and is manufactured by advanced production technology. It has the characteristics of large current capacity, low residual voltage level, sensitive response, stable performance, and reliable operation.
Installation and maintenance:
1. The lightning protection device is connected in series between the protected equipment and the signal channel.
2. The input terminal (IN) of the lightning arrester is connected to the signal channel, and the output terminal (OUT) is connected to the input terminal of the protected equipment, and cannot be reversed.
3. Reliably connect the ground wire of the lightning protection device with the ground wire of the lightning protection system.

4. This product does not require special maintenance. When the lightning protection device is suspected to be malfunctioning, the lightning protection device can be removed and then checked. If the system returns to normal after the system is restored to the state before use, the lightning protection device should be replaced.

Electrical Characteristics

Type

TRSS-485

Max continuous operating voltage(VDC) Uc

12

Voltage protective level(V)Up

20

Nominal discharge current In(8/20μS)

5kA

Max discharge current

Imax(8/20μS)

10kA

Response time ns

1

Insertion Loss


0.5dB

Adapt to data transmission rate

2Mbps

Installation method

series