Type 1 AC surge protection device TRS-A series
-
Type 1 AC surge protector
-
unipolar per phase
-
36mm width per pole
-
limp :15kA/25kA/50kA on 10/350µs
-
Remote signaling(option)
-
EN 61643-11/IEC 61643-11 compliant
The working principle of surge protection device:
The surge arresters commonly defined as SPDs (Surge Protection Devices), are devices designed to protect electric systems and equipment against transient and impulse overvoltages such as those caused by lightning strikes and by electric switching.
Their function is to divert the discharge or impulse current generated by an overvoltage to earth/ground, thereby protecting the equipment downstream.
SPDs are installed in parallel with the electric line to be protected. At the mains rated voltage, they are comparable to an open circuit and have a high impedance at their ends.
In the presence of an overvoltage, this impedance falls to very low values, closing the circuit to earth/ground.
Once the overvoltage has ended, their impedance rises again rapidly to the initial value (very high), returning to open loop conditions.
The first-level lightning protection device can discharge the direct lightning current, or discharge the huge energy conducted when the power transmission line is directly struck by lightning. For places where direct lightning strikes may occur, CLASS-I lightning protection must be carried out.
The TRS-A series type 1 SPDs are available have a impulse current capacity of 15kA, 25KA, 50KA in single-phase or 3-phase configuration and with various voltages in order to protect any type of power supply system.
THOR Type 1 DIN-rail SPD features are offering quick thermal response and perfect cut-off function and providing fast and reliable protection for various power supply systems.And its capacity to safely discharge current with 10/350 μs waveform.
TRS-A15 TRS-A25 TRS-A50
- Electrical Characteristics
Typ name
TRS-A15
SPD type
T1
Max. continuous operating ac. voltage (50 / 60 Hz) (Uc)
275V
Voltage protective level(Up) (kv)
≤ 2.0 kv
Nominal discharge current (8/20μs) (In)
15kA
Max. discharge current (8/20μs) (Imax)
---
Max impulse current(10/350μs)Iimp(kA)
15kA
Residual Current
None
Follow current
None
Other Max.voaltge can be option
320v,385v,420v,440v....
- Mechanical Characteristics
Technology
Spark gap
SPD configuration
1Pole, 2pole,3pole,4pole
Connection to Network
by screw terminals: L/N = 1.5-10mm² (16mm² rigid) or PE = 2.5-25mm² (35 mm² rigid)
Format
Plug-in modular box
Plugable
Yes
Mounting
Din rail 35 mm
Housing material
Flame retardant plastic
Working temperature
-40℃-- +70℃
Degree of protection
IP20
Response time
<25ns
Indication of invalidation
Normal: green; invalidation: red
Remote of signalling
can be option if need
Dimension
see diagram
- Electrical Characteristics
Typ name
TRS-A25
SPD type
T1
Max. continuous operating ac. voltage (50 / 60 Hz) (Uc)
275V
Voltage protective level(Up) (kv)
≤ 2.2 kv
Nominal discharge current (8/20μs) (In)
25kA
Max. discharge current (8/20μs) (Imax)
---
Max impulse current(10/350μs)Iimp(kA)
25kA
Residual Current
None
Follow current
None
Other Max.voaltge can be option
320v,385v,420v,440v....
- Mechanical Characteristics
Technology
Spark gap
SPD configuration
1Pole, 2pole,3pole,4pole
Connection to Network
by screw terminals: L/N = 1.5-10mm² (16mm² rigid) or PE = 2.5-25mm² (35 mm² rigid)
Format
Plug-in modular box
Plugable
Yes
Mounting
Din rail 35 mm
Housing material
Flame retardant plastic-
Working temperature
40℃-- +70℃
Degree of protection
IP20
Response time
<25ns
Indication of invalidation
Normal: green; invalidation: red
Remote of signalling
can be option if need
Dimension
see diagram
- Electrical Characteristics
Typ name
TRS-A50
SPD type
T1
Max. continuous operating ac. voltage (50 / 60 Hz) (Uc)
275V
Voltage protective level(Up) (kv)
≤ 2.5 kv
Nominal discharge current (8/20μs) (In)
50kA
Max. discharge current (8/20μs) (Imax)
---
Max impulse current(10/350μs)Iimp(kA)
50kA
Residual Current
None
Follow current
None
Other Max.voaltge can be option
320v,385v,420v,440v....
- Mechanical Characteristics
Technology
Spark gap
SPD configuration
1Pole, 2pole,3pole,4pole
Connection to Network
by screw terminals: L/N = 1.5-10mm² (16mm² rigid) or PE = 2.5-25mm² (35 mm² rigid)
Format
Plug-in modular box
Plugable
Yes
Mounting
Din rail 35 mm
Housing material
Flame retardant plastic
Working temperature
-40℃-- +70℃
Degree of protection
IP20
Response time
<25ns
Indication of invalidation
Normal: green; invalidation: red
Remote of signalling
can be option if need
Dimension
see diagram