Technical parameters
Contact Ratings | Form | 2Z 2H 2D | 3Z 3H 3D |
Load (resistance) | 40A/240VAC 28VDC |
Contact resistance (initial) | ≤100mΩ |
Material | Silver alloy |
Electrical life (frequency 1S on,1S off) | ≥100000 times |
Mechanical life (frequency: 300 times /1 min) | ≥ times |
Operate voltage (23℃) | DC:≤75%×rated voltage,AC:≤80%× rated voltage |
Release Voltage (23℃) | DC:≥10%× rated voltage,AC:≥30%× rated voltage |
Max voltage (23℃) | 110%×Rated Voltage |
Coil specifications | DC | 6V,9V,12V,24V,36V,48V,110V,220V (Voltage can be customized) |
AC | 6V,9V,12V,24V,36V,48V,110V,220V,380V (Voltage can be customized) |
Coil Power | DC | 2.5W |
AC | 6VA |
Operate Time | ≤25ms |
Release Time | ≤15ms |
The initial pressure | Between polar contacts | 1500VAC/1min(Leakage current 1mA) |
Between polar contacts | 1500VAC/1min(Leakage current 1mA) |
Between the contact and the coil | 2500VAC/1min(Leakage current 1mA) |
Insulation resistance | ≥500MΩ(500VDC) |
The environment temperature | -25~+55℃ |
Environmental humidity | 45%~75%RH |
The atmospheric pressure | 86~106KPa |
Resistance to stamping | 10G(Sinusoidal half-wave pulse:11ms) |
Resistance to vibration | 10~55Hz Double amplitude:1.0mm |
installation | PCB, Screw |
Outline drawing, wiring diagram, installation dimension (mm)

Small base size diagram

Bottom (A) flanged dimension drawing

Bottom (B) flange dimension drawing

Performance curve