Model: CBDL-JDX Brand: CHAOBO Protection Class: IP68 Place of Origin: Zhejiang, China Usage: Outdoor Overhead Line Application: Outdoor Overhead 5-36KV High Voltage Cable Cable diameter: 0-40mm Applicable Voltage Grade: U≥5-36KV Operation Times: ≥5000Times Ambient Temperature: -35℃≤T≤+70℃ Joint Type: Claimp Joint Type Without LED

Product Detail |
 |


Technical Parameters
Applicable voltage grade: | U≥6-35KV | Applicable wire current: | I≤1200A |
Applicable wire diameter: | 16mm sq≤D≤240mm sq | Action response time: | 0.06s≤t≤3s |
Reset time: | 6,12,24,48H (Selectable, Default 24H) | Ambient temperature: | -35℃≤T≤+70℃ |
Operation times: | ≥5000Times | Static power loss: | ≤10μW |
Protection class: | IP68 | JDG LED lumens: | 30-50Lm |
Characteristic |
 |
 The shell using high strength and high transparency aeronautical material Fully Fashioned, and treated with nanotechnology, better perspectivity. resist filth, anti-aging, without maintenance, long service life.
◆ Built-in high performance lithium battery, Service life can reach more than eight years. ◆ The circuit board using special chip and MCU etc imported Components. ◆ The shell made from aeronautical material and nano materials. ◆ The clamp with nickel plating process, best magnetic conductivity, Install and Remove with Electricity. ◆ Fault indication turn card with strong visual,it can clear instructions with light in the night, and the color not fade under sun ultraviolet light for a long time.
|
Function and Benefit |
 |
◆ Indicate the fault line and fault point quickly, lessen the blackout area;
◆ Shorten troubleshooting time,improving electricity and power supply reliability;
◆ Accurately indicate the instant fault, which is conducive to rule out the power supply problems;
◆ Providing technical means for find the hidden permanent fault point;
◆ Shorten the search time to find the fault point, reduce the labor intensity of line patrol person;
◆ Defining the responsibility of the fault area and responsible people;
◆ Avoiding traditional multiple switch out,switch on,line patrol to the effects of power equipment.
Used to judge the short circuit fault indicator diagram

As line 2# B phase 2,5,8 indicator and line 2# C phase 3,6,9 indicator turn red, but the 11,12 indicator still show white, that judged the point D happen short circuit.
Used to judge the earth fault indicator diagram

As line 2# C phase 3,6,9 indicator turn red,but the 12 indicator still show white, that judged the point D happen earth fault.
Fault Indicator Installing and Uninstalling |
 |
Fault indicator installing guide
 1.Put the indicator into the installing cup and let the spring up by U-type spring lifter. (Installing cup fixed with hot stick.) |
|  2.Fix the spring by hook in the installing cup. Make sure two spring all fixed by hook of two side.pull out the U-type spring lifter. |
|  3.After two spring all fixed by hook in the installing cup, raise up the installing cup with indicator by hot stick and upward force quickly to the cable. |
|  4.Pull down the hot stick with installing cup, the indicator would be fixed on the cable. If failed repeat from 1 step. (Be careful of falling off) |
Fault indicator uninstalling guide
 1.Fixed the installing cup on the hot stick, Turn the screw on the both side of the installing cup. Make the PVC sheet upspring |
|  2.Aim to the uninstalling indicator, then upward force, until the PVC sheet lock the indicator.
|
|  3.Pull down the hot stick slowly until the indicator is separated from the cable.
|
|  4.Turn the screw on the both side of the installing cup. Make the PVC sheet retract, take out the fault indicator. |