3 Wire 30VAC Differential Pressure Transducers 100Ω Output Impedance
3 Wire 30VAC Differential Pressure Transducers 100Ω Output Impedance
Description Operating: | -18 ~ +65°C | Storage: | -54 ~ +82°C |
---|
Electrical Connection: | PG-9 Cable Locking Device | Pressure Fitting: | 3/16" O.D.Barbed Brass Pressure Fitting For 1/4" Push-on Tubing |
---|
Zero And Span Adjustments: | Accessible Inside Of Case |
---|
High Light: | 100Ω Differential Pressure Transducers, 30VAC Differential Pressure Transducers, 30VAC Differential Pressure Detector |
PPM-WCY61-P050A Pharmaceutical Plant Low Differential Pressure Transducer
Product Introduction:
It is consisted of stainless steel diaphragm and gilt ceramic fixed electrode. When pressure changes, the space between two electrode pad also changes, which result in the change in capacitance value. And then the unique detective circuit will transfer the change of capacitance value into linear DC signal.
inherit the consistent characteristics of high-precision, rapid-response and low range. Considering the requirement of pharmaceutical plant and clean room for low differential pressure transducer, on-site LCD is developed and accessories with non-dust accumulation surface are added to meet the industrial applying requirement; so it is a desire choice for pharmaceutical plant, clean rooms of electronic factory and no-dust laboratory. low differential pressure transducer can measures pressure difference or gauge pressure (static pressure) and can choose the output signal in 4-20mA, 0-5VDC or 0-10VDC. transducer has conducted temperature compensation with an exciting voltage of 24VDC and can choose 24VAC as power supply for voltage signal product. The minimum measurement of Model 261C range is at 0 ~ 25Pa with an accuracy of ±1%FS at room temperature; The unit are temperature compensated to ±0.06%FS/°C thermal error over the temperature range +5 to +65°C.
Applications :
Pharmaceutical Plant
Clean Room
Bio-Safety Labs
Infectious Disease Room
Stairwell Fire and Smoke Protection
Technical Parameters :
Parameter Accuracy RSS* (constant temperature) | Standard ±1.0%FS | Option ±0.4%FS | Option ±0.25%FS |
Non-Linearity, BFSL | ±0.98%FS | ±0.33%FS | ±0.20%FS |
Non-Repeatability | ±0.05%FS | ±0.05%FS | ±0.05%FS |
Hysteresis | ±0.1%FS | ±0.1%FS | ±0.1%FS |
Compensation range | -5 ~ +65°C (no LCD display) |
Zero/ Span shift | <0.06%FS/°C |
Max. linear pressure | 70KPa |
Overpressure | Up to 70KPa in positive or negative direction |
Warm up drif | ±0.1% FS |
Error caused by installing position (the nominal position in factory is in vertical position) | Range | Zero Drift (%FS/G) |
0-25Pa | 2.1 |
0-250Pa | 0.22 |
0-1250Pa | 0.14 |
0-7500Pa | 0.06 |
* RSS of non-linear, hysteresis and non-repeatability |
Environmental and Physical Data
Operating | -18 ~ +65°C |
Storage | -54 ~ +82°C |
Electrical connection | PG-9 cable locking device |
Pressure Fitting | 3/16” O.D.Barbed Brass pressure fitting for 1/4” push-on tubing |
Zero and Span adjustments | Accessible Inside of Case |
Pressure medium | Air or similar non-conducting gas |
Enclosure | Cast aluminum |
Weight | 347.5g |
Mounting | φ3mm bolt or countersunk head bolt (option) |
Electrical Data (Voltage)
Circuit | 3-Wire (Com, Exc, Out) |
Exciting | 9 ~ 30VAC/12 ~ 42VDC (0 ~ 5VDC output); 12 ~ 30VAC/13 ~ 42VDC (0 ~ 10VDC output) |
Output* | 0-5VDC/0-10VDC** |
Bidirectional Output at Zero | 2.5VDC(0-5VDC) / 5VDC(0-10VDC) |
Output Impedance | 100Ω |
*Calibrated into a 50KΩ load, operable into a 5KΩor greater.
** Zero output factory set to within ±50mV (± 25mV for option accuracy)
** Span(Full scale) output factory set to within ±50mV (± 25mV for option accuracy)
Electrical Data (Current)
Circuit | 2-Wire Protected from Miswiring |
Full scale output* | 20mA±0.16mA |
Zero point output* | 4mA±0.16mA |
Bidirectional Output at Zero | 12mA |
External load | 0-800Ω |
Min. supply voltage | 9+0.02×(Resistance of receiver plus line)VDC |
Max. supply voltage | 30+0.004 × (Resistance of receiver plus line)VDC |
* Calibrated with a 24VDC loop supply voltage and a 250 ohm load
Definition of wiring: