SF6 Sulfur Hexafluoride Comprehensive Tester

Model
Nature of the Manufacturer
Manufacturer
Product Category
HV Switch Tester
Place of Origin
City, Province
Overview
★Quick and gas-saving: dew point takes 5 minutes, purity/decomposition product takes 2 minutes★Self-locking joint: imported self-locking joint from Germany, no air leakage★Data storage: up to 200 sets of test data can be stored★Curve function: large-screen curve display dew point measurement process★Purity: 0%~99% ±0.5%★Dew point: -80℃~+20℃ ±0.5℃(-80℃~-60℃)63% takes 10 seconds, 90% takes 240 seconds/63% takes 5 seconds, 90% takes 45 seconds★H2S:0~200ppm Accuracy:±0.5% 0.1ppm★SO2:0~200ppm Accuracy:±0.5% 0.1ppm★CO:0......
Product Details

Function introduction

SF6 Sulfur hexafluoride comprehensive tester, integrates the testing of SF6 humidity, SF6 purity, and SF6 decomposition products, and integrates the functions that can only be realized by three instruments into one instrument. One on-site measurement can complete the detection of three indicators, which greatly saves the gas in the equipment, reduces the workload of users, and improves work efficiency.

The reason why this instrument has excellent performance is that all the best sensors from abroad are used; the humidity uses purely imported high-precision humidity sensors, the purity uses thermal conductivity sensors with temperature compensation, and the decomposition products also use sensors imported from Europe. Color LCD display, real-time display of various parameters, full touch control, fool-like operation, massive information storage, built-in rechargeable battery, AC and DC dual-use.


Features

Ø1.Self-calibration: The sensor probe can automatically calibrate the zero point, automatically eliminate the system error caused by zero point and drift, and ensure the accuracy of each measurement.

Ø2.Easy to operate, super large touch LCD screen, WYSIWYG simple operation.

Ø3.The pipeline cleaning device is optional, and the internal pipeline is automatically cleaned after the test to improve the test speed and accuracy

Ø4.Fast and gas-saving: After starting up and entering the measurement state, the dew point measurement time is about 3 minutes each time.

Ø5.Self-locking connector: The original imported self-locking connector is used, which is safe and reliable without air leakage.

Ø6.Data storage: It adopts large-capacity design and can store up to 1000 sets of test data.

Ø7.Clear display: 7-inch super large touch LCD screen directly displays dew point, micro water (ppm), SF6 purity, SO2, H2S, CO content, ambient temperature, ambient humidity, time and date, etc.

Ø8.Built-in USB interface, which can be connected to a PC, and all internal data of the instrument can be uploaded to the computer through supporting software, which is convenient for data analysis.

Ø9.Built-in super-capacity rechargeable lithium battery, which can work continuously for more than 12 hours on a single charge.


Technical parameters

purity

Measuring range

0%~99%

measurement accuracy

±0.5%

measure time

<>

dew point

Measuring range

-80 ℃~+20 ℃

measurement accuracy

±0.5℃(-80℃~-60℃)

Response time

(+20℃)

63% takes 5 seconds, 90% takes 45 seconds(-60℃~+20℃)

63% takes 10 seconds, 90% takes 240 seconds(+20℃~-60℃)

H2S

Measuring range

0~200ppm

minimum detection

≤0.1ppm

Accuracy

±0.5%

stability

0~200ppm

repeatability

≤2%

SO2

Measuring range

0~200ppm

minimum detection

≤0.1ppm

Accuracy

±0.5%

stability

0~200ppm

repeatability

≤2%

CO

Measuring range

0~1000ppm

minimum detection

≤1ppm

Accuracy

±0.5%

stability

0~1000ppm

repeatability

≤2%

ambient temperature

-40℃~+60℃

environment humidity

0~100% RH

power supply

AC 100~240V 50/60Hz

built-in rechargeable battery

battery performance

Charging time: 10 hours; use time more than 12 hours.

Operating temperature

-30℃~+70℃

size

280×190×300 mm

weight

7.6KG


Measurement

1. Connecting SF6 equipment

1)Connect the threaded end of the measuring pipe to the switch joint and tighten with a wrench;

2)Close the flow regulating valve on the front panel of the host;

3)Insert one end of the quick connector on the test pipe into the air inlet on the decomposition detector;

4)Connect the exhaust pipe to the air outlet;


2. check battery

When the internal battery is used for power supply, the upper right corner will display the battery power. If the power shows a red power-out sign, please charge it as soon as possible before continuing to use it.

The instrument can be used while charging, but the charging time will be greatly extended.


3. start measuring


start measuring


①Turn on the power, the instrument will automatically initialize. After completing the self-calibration, it will automatically enter the measurement state.

②Confirm that the high-precision regulating valve on the instrument is closed, and test the quick plug of the pipeline

③Insert into the air inlet of the instrument.

④Connect the other end of the test pipe to the gas supply port (or test port) of the device under test.

⑤At this time, open the regulating valve on the front panel of the instrument, and then adjust the gas flow.

⑥It takes 5-10 minutes for the first measurement (SF6 micro-water), and then only 3-5 minutes for each subsequent measurement.

⑦When measuring SF6 dew point alone, adjust the flow rate to about 0.5 SLM (standard liter per minute).

⑧When measuring SF6 purity, H2S, SO2 and CO content, the flow rate should be adjusted to about 0.2 SLM (standard liter per minute).


4. Storing data


Storing data


Precautions

1. SF6 Sulfur hexafluoride comprehensive tester should be placed in a safe place to prevent it from being broken and violent vibration.

2. The instrument should be charged in time before use.

3. When charging, you only need to connect the power cord to the AC socket, without turning on the power switch, the instrument will automatically charge, and the charging time generally takes more than 10 hours.

4. The high-capacity lithium battery is used inside the instrument because of the characteristics of the battery. Therefore, it is recommended that when the instrument is not used for a long time, it can be charged once every 1 to 2 months. To maintain the activity of the lithium battery.

5. If the instrument is not in use, it should be put into an aluminum alloy packing box and placed on the test bench or instrument rack to prevent dust and moisture.

6. The instrument is calibrated once a year with standard gas. It can be sent to the manufacturer or authorized unit for calibration to ensure accuracy.

7. When the concentration of SO2 and H2S in the detection gas is high, the pipeline should be cleaned with clean gas (air or nitrogen), and the inside of the instrument should be cleaned before the next measurement.

8. When the concentration of SO2 or H2S in the detection equipment exceeds the normal value, it is recommended to measure twice to confirm the result.


Sulfur hexafluoride circuit breaker water content measurement requirements

Test content

standard (ppm , 20℃)

The moisture content of the breaking unit and the pillar unit should be measured separately when the sulfur hexafluoride circuit breaker is out of the factory and during overhaul (before the overall installation).

≤150

During handover, measure the moisture value of the circuit breaker by the gas interface at the lower part of the pillar

≤150

During operation, the moisture value of the circuit breaker is measured by the gas charging interface at the lower part of the pillar. The test period shall be stipulated in the "pre-test procedure".

≤200

During operation, if necessary (air leakage of the breaking unit, disassembly of the breaking unit), the water content of the breaking air chamber of the sulfur hexafluoride circuit breaker should be measured separately from the self-sealing joint in the header.

≤300