★320×240 large-screen LCD display★Fully automatic (manual) collection, measurement, display, storage★Built-in high-precision real-time clock function★store 200 sets and print real-time measurement data and characteristic curves★perfect overvoltage and overcurrent protection functions★Concurrently perform no-load and short-circuit tests
Product Details
product description
Turn-to-turn short circuit of generator rotor windings is a common fault in power systems. When such a fault occurs, the rotor current increases and the winding temperature increases, limiting the output of the generator, and in severe cases, it will affect the normal operation of the generator. Turn-to-turn shorts are usually identified by measuring the AC impedance and power losses of the generator rotor windings. The traditional measurement method is to use multiple test instruments and measure them after they are assembled in the field. This method, which requires a lot of test instruments to set up a measurement system, has the disadvantages of cumbersome test equipment, time-consuming and laborious, complicated data sorting, and low measurement accuracy.
With the continuous development of digital signal processing technology, new microprocessors and algorithms are constantly emerging. Based on this, we have developed a generator rotor AC impedance tester based on digital signal processor DSP. Generator Rotor Impedance Tester takes the digital signal processing system as the hardware platform, and fully utilizes the computing power of the digital signal processor, which greatly improves the calculation speed and calculation accuracy of the instrument, and provides a guarantee for the normal operation of the power system.
Features
1. Fully automatic (manual) collection, measurement, display, storage and printing of all measurement parameters and AC impedance characteristic curves;
2. Real-time display of measurement data and AC impedance characteristic curve, convenient for storage and printing;
3. Using 320×240 large-screen LCD display, Chinese menu prompts, easy to operate;
4. Built-in large-capacity non-volatile memory: can store 200 sets of measurement data and curves;
5. Built-in high-precision real-time clock function: date and time calibration can be performed;
6. Built-in high-speed micro thermal printer: can print measurement and historical data;
7. Concurrently perform no-load and short-circuit tests of single-phase transformers and volt-ampere characteristic tests of voltage (current) transformers and arc suppression coils;
8. Generator Rotor Impedance Tester has perfect overvoltage and overcurrent protection functions, among which the overvoltage and overcurrent protection value is automatically adjusted according to the setting of the test parameters, which is simple and can ensure the safety of the tested equipment.
Technical parameters
1. Measurement range Impedance: 0~999.9Ω
Voltage: 0~600V
Current: 0~120A
Power: 0~72kW
Frequency: 45~65Hz
2. Accuracy Impedance, voltage, current, frequency: class 0.2
Power: 0.5 class
3.Dimensions 345mm×295mm×175mm
4. Instrument weight 5kg
5. Ambient temperature -10℃~50℃
6. Ambient humidity ≤85%RH
7. Working power AC220V±10%
8. Power frequency 50±1Hz
panel introduction
1. Power input: The input terminal of the test circuit is connected to the output end of the test voltage regulator;
2. Current output: the current measurement terminal of the test loop, the range is 0 ~ 120A;
3. Voltage input: the voltage measurement terminal of the test loop, the range is 0 ~ 600V;
4. Power switch: the power switch and insurance of the instrument;
5. Grounding column: dedicated to the safety grounding of the instrument;
6. LCD screen: used to display various data and curves;
7. Keyboard: used for operation and parameter setting of various functions;
8. Printer: used to quickly print various data and curves;
9. Buzzer: used for over-limit, over-voltage and over-current alarms;
10. RS-232: used for data communication between the instrument and PC (as an upgrade solution).
11. USB interface: used for large-capacity external storage (used as an upgrade solution).
Precautions
1. Please read the instruction manual carefully before using the instrument, and check that the wiring is correct and the grounding is good.
2. During the test, the voltage regulator should be slowly boosted near the test point to ensure the reliability of data acquisition.
3. If overvoltage or overcurrent protection occurs during the test, the cause must be found out and the abnormal situation is eliminated before continuing the test; do not operate blindly to avoid unnecessary losses.
4. After the measurement is completed and the measurement state is exited, the wiring can be removed.