Circuit Breakers with Electronic Over Current ReleaseThe feature discriminating electronic circuit breakers from thermal-magnetic breakers is to control the over current releases with electronic is circuit. Electronic is control is performed via microprocessor.During design of the electronic circuit,worst possibilities to encounter in operation have been taken into consideration. In high circuit currents, direct opening has been ensured without operating electronic circuit. In this way, possibility of failure in th......
Advantages
• Wide range:100A to 1600A(AC)
• Compact dimensions
• Adjustable thermal setting(40-99%)In.
• Adjustable magnetic setting(1.5-12times)In.
• Push to trip button provision.
• Separate main and arcing contacts
• Wide range of accessories.
Electronic Release Characteristic Curve

Electronic Release(Electronic Trip Unit)

Physical Parameters Of Dam1 Mccb Molded Case Circuit Breaker
Category (EN 60947-2/IEC 60947-2) | Endurance | | |
Model | Pole | Dielectric Propery (V) | Total Cycles | Total Cycles | Electrical Life | Mechanical Life | Main circuit | Auxiliary circuit |
DAM1-250 | 3P /4P | 3000 | ≤30/0※ | 8000 | 1000 | 7000 | A/B | AC-15 |
DAM1-630(400) | 3P /4P | 3000 | 60/0※ | 5000 | 1000 | 4000 | A/B | AC-15 |
DAM1-800 | 3P /4P | 3000 | ≤80/0※ | 5000 | 1000 | 4000 | A/B | AC-15 |
DAM1-1600 | 3P /4P | 3000 | ≤80/0※ | 3000 | 500 | 2500 | A/B | AC-15 |
Size of MCCB Molded Case Circuit Breaker
Model | Pole | Outline dimension (LXWXH) |
DAM1-250 | 3P | 212.5x105x103.5mm |
DAM1-630(400) | 3P | 254x140x103.5mm |
4P | 254x184x103.5mm |
DAM1-800 | 3P | 268x210x103.5mm |
4P | 268x280x103.5mm |
DAM1-1600 | 3P | 406x210x138.5mm |
4P | 406x280x138.5mm |