DAM2 Electronic MCCB

Model
Nature of the Manufacturer
Manufacturer
Product Category
DAM2 Moulded Case Circuit Breaker
Place of Origin
City, Province
Overview
Product Details

Introduction

DAM2E CM1 Electronic adjustable moulded case circuit breaker has three protection function, the circuit breaker with utilization category B connected with other short-circuit protection device in the same circuit has completely optional under short circuit circumstance; With five tripping features, the user can set the equipment through the shunt release according to the load current, electronic shunt release is powered by circuit breaker itself; current signal and control power is from the circle circuit transformer installed in the circuit breaker; With fire protection shunt release for alarming but not trip, when the load current is overloaded, the circuit breaker does not trip, and output the passive contact, driving the corresponding alarm device; The dimensions and specifications are the same as those of DAM2 CM1 series MCCB, the installation can be changed.

Application

1. The elevation of the installation site is not more than 2000m.
2. The ambient temperature is not more than +40℃, and the average temperature within 24h is not more than +35℃, the lower limit of the ambient temperature is -5℃.
3. When the max temperature is +40℃, the relative humidity of air is not more than 50%, can allow a higher relative humidity at a lower temperature, such as 90% at 20℃, special measures should be taken for the condensation produced occasionally on the product due to temperature changes.
4. The pollution degree is 3.
5. The circuit breaker installation of main circuit category is class III, the installation category of auxiliary circuit and control circuit not connect to the main circuit is II.
6. Use category is A or B.

Important information

1) No code for circuit breaker for distribution, 2 for circuit breaker for protecting motor.
2) No code for handle direct operation, P for electric operation, Z for the rotating handle.
2. Classification
A. According to the rated limit short-circuit breaking capacity, divided into standard (S), high breaking (H);
B. According to the mode of connection, divided into three types: front connection, rear connection and plug-in;
C. According to the pole, divided into three-poles and four-poles. The N-phase of the 4-pole products is not equipped with the overcurrent release, and the N-phase is on-off with the other phase;
D. According to the accessory device, divided into with accessory device and without accessory device: accessory device is divided into internal and external devices: the internal device has shunt release, under voltage release, auxiliary contact, alarm contact, the external device has rotating handle operating mechanism, electric operation mechanism etc..

Accessory NameAccessory CodeTripping Mode
-300Electric Tripping Unit
Alarm Contact308
Shunt Release310
Auxiliary Contact320
Undervoltage Release330
Shunt Release + Auxiliary Contact340
Shunt Release + Undervoltage Release350
Two Groups of Auxiliary Contacts360
Auxiliary Contact + Undervoltage Release370
Alarm Contact + Shunt Release318
Alarm Contact + Auxiliary Contact328
Undervoltage Release + Alarm Contact338
Auxiliary Contact + Alarm Contact + Shunt Release348
Two Groups of Auxiliary Contacts + Alarm Contact368
Undervoltage Release + Auxiliary Contact + Alarm Contact378

Note: 1. DAM2E-100, 225 only have accessories of 308, 310, 320, 330, 328;
2. DAM2E-400 only have 3-pole accessories of 308, 310, 320, 330, 328;
3. DAM2E-400 only have no 4-pole accessories of 350, 318, 338, 348, 378.

in the setting, the dial switch must be set in place!

1. Adjust overload long delay action current Ir1, according to the different circuit breaker rated current, 4-10 files can be adjusted;
2. Adjust long delay action time t1, 4 files can be adjusted;
3. Adjust short-circuit short-delay action current Ir2, 9 files can be adjusted;
4. Adjust short delay action time t2, 4 files can be adjusted;
5. Adjust short-circuit instantaneous action current Ir3 action, 9 files can be adjusted;
6. Adjust pre-alarm action current Ir0, 7 files can be adjusted.

Technical parameters

The setting range of intelligent controller is shown in the table

Setting ProjectSetting Range
Setting value of overload long delayCurrent setting value lr1(30~100)A,(100~250)A,(200~400)A,(400~630)A,(630~800)A,(800~1250)A
Time setting value t1(12、60、80、100)s
Setting value of short circuit and short delayCurrent setting value lr2(2~12)In
Time setting value t2(0.06, 0.1, 0.2, 0.3)s
Setting value of instantaneous short circuitCurrent setting value lr3(4~14)In

The main technical data of circuit breaker are shown in table

ModelDAM2E-100DAM2E-250DAM2E-400DAM2E-630DAM2E-800DAM2E-1250
Frame Current Inm(A)1002504006308001250
Breaking CapacityLMLMLMMHMHH
Rated Current In(A)63,80,100225,250300,400500,630700,8001000,1250
Pole3,43,43,43,43,43,43,43,43,43,43,4
Rated Operational Voltage Ue(V)AC400
Rated Insulation Voltage Ui(V)800
Rated Impulse Withstand Voltage Uimp(V)8000
Rated limit short circuit breaking capacity Icu(kA)5085508565100651006510080
Rated running short circuit breaking capability Ics(kA)3550355042654262426250
Rated short-time withstand current Icw/0.5s(kA)--581015/1S
Usage CategoryAABBBB
Flashover Distance (mm)≤50≤50≤100≤100≤100
Operating PerformancePower-on (Times)150010001000500500500
Power-off (Times)850070004000300030003000

Characteristics of release

a. Characteristics of Electric Trip Unit
With overload long-delay inverse time, short-circuit short-delay inverse time, short-circuit short delay time limit, short-circuit instantaneous action and other protection features, the protection characteristics can be set up by the users.
b. Overload long delay inverse time protection action characteristics in Table 4.
c. Short-circuit short-delay protection action characteristics in Table 5.
d. Short-circuit instantaneous protection action characteristics in Table 6.

Controller TypesBasic typeIntelligent communication type, programming communication type, liquid crystal type
CurrentAction Time
1.05lr1No action within 2 hours
1.3lr1≤1h action
2lr1Inm=100A, 250A Setting time t1(s)t1=(12, 60, 80, 100)s12s-100s(most progress 1s)
Inm=400A, 630A, 800A Setting time t1(s)t1=(12, 60, 80, 100)s12s-100s(most progress 1s)
Thermal Memory30min, can be cleared after power off (this function is optional function in intelligent communication type and programming communication type)

1. Action time I²t1 = (2Ir1) ²t1 (1.2Ir1≤I 2. Action time tolerance is ± 20%;
3. Returnable time is not less than 70% action time.

Short delay overcurrent protection characteristics

CurrentAction Time
Ir2≤I<1.5Ir2Inverse TimeI²t2=(1.5Ir2)²t2
1.5Ir2≤I<Ir3Definite timeSetting time t2(s)0.060.10.20.3
Tolerance (s)±0.02±0.03±0.04±0.06
Returnable time (s)0.21

Note: Inverse time action time tolerance is ± 20%.

Short-circuit instantaneous protection action characteristics

Rated Current100, 225(250)400, 630800
Setting CurrentIr3=4, 6, 7, 8, 10,
11, 12, 13, 14
Ir3=4, 6, 7, 8, 10,
11, 12, 13, 14
Ir3=4, 5, 6, 7, 8,
9, 10, 11, 12
Operation CharacteristicsI≤0.85Ir3 non-operation
I≥1.15Ir3 operatino

Technical data of accessory device

a. Rated values of auxiliary contacts and alarm contacts are shown in table

TypeFrame Rated Current
Inm(A)
Conventional Thermal Current
Ith(A)
Rated Operational Current Ie(A)
AC400VDC220V
Auxiliary ContactInm≤40030.30.15
Inm≥40030.40.15
Alarm Contact100≤Inm≤80030.30.15

b. The rated control power supply voltage (Us) and rated operating voltage (Ue) of the control circuit release and electric mechanism are shown in Table 8

TypeRated Voltage (V)
AC50HzDC
ReleaseShunt ReleaseUs220/380110、220
Undervoltage ReleaseUe220/380-
Electric MechanismUs220/380110、220

c. When the applied voltage of the shunt release is between 70%~99% of the rated power voltage, the circuit breaker should be reliably broken.
d. When the power voltage drops to 70% ~ 35% of the rated voltage of the undervoltage release, the undervoltage release can reliably break the circuit breaker; When the power voltage is lower than 35% rated voltage of the undervoltage release, the undervoltage release can prevent the circuit breaker from closing; When the power voltage is higher than 85% rated voltage of the undervoltage release, the undervoltage release can ensure the reliable closing of the circuit breaker.
e. Electric operating mechanism at the rated frequency, between 85% ~ 110% power voltage, the circuit breaker can be reliably closed.

Outline and Installation Dimensions

1. The dimensions are shown in figure 3~figure 6 and the table

(1) Dimensions of front connection see Figure 3 (X-X, Y-Y is the center of 3P circuit breaker)

ModelDAM2E-100DAM2E-250DAM2E-400DAM2E-630DAM2E-800
Front ConnectionW92107150210
W1607096140
L150165257280
L1100132220240
L2132144244243
H9390107116
H1112110147155
H229243846
H31259.515
H4446.55
E55659283
F25256868
G18223044
W2122142198280
W390105144210
M1M8M8M10M10M12

(2) Dimensions of rear connection see Figure 4 and 5
(3) Dimensions of plug-in type front connection see Figure 6
(4) Dimensions of plug-in type rear connection see Figure 7

ModelDAM2E-100DAM2E-250DAM2E-400DAM2E-630DAM2E-800
Rear ConnectionL4164173267295
H553556884
H693100128-
H735353737
M1M8M8M10M10M12
d-8.510.513
t--8.516
Plug-in ConnectionL6168183279296
H850506061
H964728497
H107687107148
H1118182116
M1M8M8M10M10M12
M2M6M6M6M8M8
L7220252357-
L8250276387-

2. Dimensions for mounting plate opening

(1) Dimensions of front connection see Figure 8 (X-X, Y-Y is the center of 3P circuit breaker)

ModelDAM2E-100DAM2E-250DAM2E-400DAM2E-630DAM2E-800
Pole343434343
Dimensions for mounting plate opening (mm)A3035447070
B129126194243303
d4.54.5777

(2) Dimensions of rear connection see Figure 9 (X-X, Y-Y is the center of 3P circuit breaker)

ModelDAM2E-100DAM2E-250DAM2E-400DAM2E-630DAM2E-800
Pole3434343434
Dimensions for mounting plate opening (mm)A60-70-96-140-
A1-90-105-144-210
B72-87-124-178-
B1-102-122-172-248
C9093164158
D132144224243
Φ122243248
Φ25.55.56.57

ModelDAM2E-100DAM2E-250DAM2E-400
Pole333
Dimensions for mounting plate opening (mm)A92107150
B607060
C5654129
D3863.262
E9294109
d6.56.58.5

(4) Dimensions of plug-in type rear connection see Figure 10 (X-X, Y-Y is the center of 3P circuit breaker)

ModelDAM2E-100DAM2E-250DAM2E-400DAM2E-630DAM2E-800
Pole3434343434
Dimensions for mounting plate opening (mm)A94-110-152-215-
A1-125-145-200-283
B60-70-60-140-
B1-90-105-108-210
C5654129143
D48586565
E9088166183
d6.56.58.510