>> Introduction
DAB5-63 are intended for protecting distribution and group systems having different loads:
- electric appliances, lighting – V characteristic switches;
- drives with moderate starting currents (compressor, fan group) - C characteristic switches;
- drives with high starting currents (hoisting mechanisms, pumps) - D characteristic switches;
Miniature circuit breaker DAB5-63 are recommended for use in electrical distribution panels of residential and public buildings.
>> Advantages
· Two types of short circuit protection.
· Wide range of operating temperatures from –40 to +50° С.
· Updated wider engagement lever with improved contact area.
· Notches on terminal clamps provide for lowering thermal losses and boosting the mechanical stability of connection.
| MCB DAB5-63 | | | | |
| For protection of general power distribution (IEC/EN 60898-1) | 
| 
|  | |
| Poles | 1P | 2P | 3P | 4P |
| Electrical performance |
| Functions | short circuit protection,overload protection,isolationg,control |
| Rated frequency f (Hz) | 50-60Hz |
| Rated working voltage Ue V AC | 230/400 | 400 |
| Rated current In(A) | 6,10,16,20,25,32,40,50,63 |
| Rated insulated voltage Ui (V) | 500 |
| Impulse withstand voltage Uimp (kV) | 4 |
| Instantaneous tripping type | DAB5-63N | B/C/D |
DAB5-63H | B/C/D |
| Rated short circuit Icn(kA) | DAB5-63N | 4.5 |
DAB5-63H | 6 |
| Release type | | Thermal magnetic type |
Service life(O~C) | Mechanical | Actual value | 20000 |
| Standard value | 4000 |
Electrical | Actual value | 8000 |
| Standard value | 4000 |
| Connection and installation |
| Protectiom degree | IP20 |
| Wire mm² | 1~35 |
| Working temperature | -5 ~+40℃ |
| Resistance to humidity and heat | Class 2 |
| Altitude above sea | ≤2000 |
| Relative humidity | +20℃ , ≤90% ;+40℃ , ≤50% |
| Pollution degree | 2 |
| Installation environment | Avoid obvious shock and vibration |
| Installation class | Class Ⅱ , Class Ⅲ |
| Mounting | DIN35 rail |
| Combination with accessories |
| Auxiliary contact | Yes |
| Alarm contact | Yes |
| Shunt release | Yes |
| Undervoltage release | Yes |
| Auxiliary contact+Alarm contact | Yes |
Dimensions(mm) (WxHxL) | a | 17.5 | 35 | 52.5 | 70 |
b | 80.2 | 80.2 | 80.2 | 80.2 |
c | 76.5 | 76.5 | 76.5 | 76.5 |