DAB7N-40 Series miniature circuit breaker adopts double-break point of 1P+N,the two poles are insulated and isolated from each other,under synchronous operation,N-pole always will make first and break later, which guarantees electric arc breaking capacity of protected pole, also ensures safety of controlled circuits and electric equipment.
Advantages
• Two types of overcurrent protection – thermal and electromagnetic.
• Independent contact position indicator.
• DIN rail latch with a double fixed position.
• Wide range of operating temperatures from –40 to +50° С.
• Wide engagement lever with improved contact area.
• Notches on terminal clamps lower thermal losses and boost the mechanical stability of connection.
Electrical Parameters of DAB7N-40 Min iature Circuit Breaker
Standard of conformity: IEC60898, GB10963
Rated power: 50-60HZ
Rated voltage: 230V
Rated current: 40A
Rated insulation voltage: 500V
Impulse withstand voltage: 4KV
Endurance: no less than 180,000 times of on-off
Instantaneous trip type: B/C
Rated breaking capacity: 6
Release type: thermo-magnetic
Mechanical Parameters of DAB7N-40Miniature Circuit Breaker
Protection grade: IP20
Electric wire: 1~35mm2
Working temperature: -5~+40℃
Flame retardant grade: grade2
Altitude: ≤2000
Class of pollution: 2
Installation environment: Avoid obvious shock and vibration
Installation grade: grade II
Installation method: Using 35mm guide rail according to IEC standard
Terminal type: Dual-purpose terminal can be connected to the bus bar and conductor.
Terminal connection ability: conductor 1-25mm2, bus bar thickness 0.8-2mm
Guide rail: DIN35guide rail
Technical Features
| MCB DAB7-40 |
| For protection of general power distribution (IEC/EN 60898-1) |  |
| Poles | 1P |
| Electrical performance |
| Functions | short circuit protection,overload protection,isolationg,control |
| Rated frequency f(Hz) | 50-60Hz |
| Rated working voltage Ue(V)AC | 230 |
| Rated current In ( A) | 40 |
| Rated insulated voltage Ui( V) | 500 |
| Impulse withstand voltage Uimp(kV) | 4 |
| Instantaneous tripping type | B/C |
| Rated short circuit Icn(kA) | DAB7-40 | 6 |
| Release type | Thermal magnetic type |
| Service life(O~C) | Mechanical | Actual value | 12000 |
| Standard value | 4000 |
Electrical | Actual value | 6000 |
| Standard value | 4000 |
| Connection and installation |
| Protectiom degree | IP20 |
| Wire mm² | 1~35 |
| Working temperature | -5~+40℃ |
| Resistance to humidity and heat | Class 2 |
| Altitude above sea | ≤2000 |
| Relative humidity | +20℃,≤90% ;+40℃,≤50% |
| Pollution degree | 2 |
| Installation environment | Avoid obvious shock and vibration |
| Installation class | ClassⅡ, ClassⅢ |
| Mounting | DIN35 rail |
| Combination with accessories |
| Auxiliary contact | Yes |
| Alarm contact | Yes |
| Shunt release | Yes |
| Undervoltage release | Yes |
| Auxiliary contact+Alarm contact | Yes |
| Dimensions(mm) (WxHxL) | a | 18 |
b | 80.7 |
c | 72 |