Advantages
• Trip Free mechanism
• High Breaker capacity 15KA
• Positive contact indication
• Thermal and magnetic trip function
• Current limiting design for short circuit fault protection
• CE marking,Semko product
• Specification:IEC 60947-2
Design Features
Large Cable Terminals Suitable for copper and aluminum cables, these terminals are compatible with cables upto 35mm2 cross section area.
Technical Features
| MCB DAB7-125 |
| For protection of general power distribution (IEC/EN 60947-2) | | |  |  |
| Poles | 1P | 2P | 3P | 4P |
| Electrical performance |
| Functions | short circuit protection,overload protection,isolationg,control |
| Rated frequency f ( Hz) | 50-60Hz |
| Rated working voltage Ue (V) AC | 230/400 | 400 |
| Rated current In (A) | 6,10,16,20,25,32,40,50,63,80,100,125 |
| Rated insulated voltage Ui (V) | 500 |
| Impulse withstand voltage Uimp( kV) | 4 |
| Instantaneous tripping type | DAB7-125N | B/C/D |
DAB7-125H | B/C/D |
| Rated short circuit Icn(kA) | DAB7-125N | 10 |
DAB7-125H | 15 |
| Release type | Thermal magnetic type |
| Service life(O~C) | Mechanical | Actual value | 8500 |
Standard value | 4000 |
Electrical | Actual value | 1500 |
Standard value | 1000 |
| Connection and installation |
| Protectiom degree | IP20 |
| Wire mm² | 1~35 |
| Working temperature | -5~+40℃ |
| Resistance to humidity and heat | Class 2 |
| Altitude above sea | ≤2000 |
| Relative humidity | +20℃,≤90% ;+40℃,≤50% |
| Pollution degree | 2 |
| Installation environment | Avoid obvious shock and vibration |
| Installation class | ClassⅡ, ClassⅢ |
| Mounting | DIN35 rail |
| Dimensions(mm)(WxHxL) | a | 27 | 54 | 81 | 108 |
b | 90 | 90 | 90 | 90 |