Categories AC Miniature Circuit Breakers Brand Kayal Model @Model["xinghao"] FOB Port Ningbo/Shanghai Terms of Payment Western Union,T/T,Paypal Update 2021/04/02
NC-100 MINI CIRCUIT BREAKER
GENERAL
1.1Application:
For protecting equipment against overload and short circuit
1.2General rules for choosing MCB
Technicala data of the network at the point considered:
The earthing systems(TNS,INC),Shrot-circuit current at the circuit-breaker installatino point,which must always be less than the breaking capacity of this device,Networl normal voltage.
| | Standard | | IEC/EN 60947-2 |
| Electrical features | Rated current In | A | 63,80,100,125 |
| | Poles | | 1P,2P,3P,4P |
| | Rated voltage Ue | V | 230/400 |
| | Insulation voltage Ui | V | 500 |
| | Rated frequency | Hz | 50/60 |
| | Rated breaking capacity | Ka | 6~10 |
| | Rated impulse withstand voltage(1.2/50)Uimp | V | 6000 |
| | Dielectric test voltage at ind.Freq.for 1 min | Kv | 2.5 |
| | Pollution degree | | 3 |
| | Thermo-magnetic release characteristic | | 8-12In |
| Mechanical | Electrical life | | 1500(In=63A,80A,100A) |
| features | | | 1000(In=125A) |
| | Mechanical life | | 8000(In=63A,80A,100A) |
| | | | 7000(In=125A) |
| | Contact position indicator | | Yes |
| | Pollution degree | | IP20 |
| | Standard | | IEC/EN 60947-2 |
| | Reference temperature for | ℃ | 30 |
| | setting of thermal element | | |
| | Ambient temperature | ℃ | -5...+40 |
| | | | (Special application please refer to P29 |
| Combination | (with daily average≤35℃) | | for temperature compensation correction) |
| with | Storage temperation Terminal connection type | ℃ | -25..+70 |
| sccssorles | | | Cable/pin-type busbar |
| | Terminal size top/bottom for cable | mm2 | 50 |
| | | AWG | 18-1/0 |
| | Terminal size top/bottom for busbar | mm2 | 50 |
| | | AWG | 18-1/0 |
| | Tightening torque | N*m | 3.5 |
| | | In-Ibs. | 3.1 |
| | Mounting | | On DN rail EN 60715(35mm) |
| | | | by meas of fast clip device |
| | Connection | | From top |
| | Auxilary contact | | |
| | Auxilary contact | | Yes |
| Rated current | Temperature compensation coefficient under various operational temperature | | | | | | | | |
| In (A) | | | | | | | | | |
| | -10℃ | 0℃ | 10℃ | 20℃ | 30℃ | 40℃ | 50℃ | 55℃ | 60℃ |
| 63 | 1.28 | 1.21 | 1.14 | 1.07 | 1 | 0.84 | 0.87 | 0.85 | 0.82 |
| 80 | 1.22 | 1.16 | 1.11 | 1.05 | 1 | 0.95 | 0.91 | 0.88 | 0.86 |
| 100 | 1.22 | 1.18 | 1.11 | 1.05 | 1 | 0.95 | 0.91 | 0.88 | 0.88 |
| 125 | 1.22 | 1.16 | 1.11 | 1.05 | 1 | 0.95 | 0.91 | 0.88 | 0.86 |