It is used in overhead electrical transmission and distribution, for grounding electrical systems where high conductivity and flexibility is required. Suitable for numerous other applications.
Product Details
Construction Bare stranded soft-drawn copper conductor is a concentric-lay-stranded conductor consisting of hard-drawn copper wires available in both single layer and multi-layer constructions.
Application It is used in overhead electrical transmission and distribution, for grounding electrical systems where high conductivity and flexibility is required. Suitable for numerous other applications.
Applicable Standard Internation IEC 60228
Dimension Characteristics
Section
Stranding
Overall Diameter
Conductor Weight
DC. Electrical Resistance at 20°C
mm2
No.
Φmm
mm
kg/km
Nominal
Max.
Ω/km
10
7
1.35
4.05
89.82
1.788
1.829
14
7
1.60
4.80
126.20
1.273
1.303
16
3
2.65
5.70
148.30
1.082
1.106
16
7
1.70
5.10
142.40
1.128
1.154
25
7
2.10
6.30
217.30
0.7391
0.7563
32
3
3.75
8.06
296.90
0.5405
0.5520
32
7
2.46
7.38
298.20
0.5386
0.5497
35
7
2.50
7.50
308.00
0.5215
0.5337
50
7
3.00
9.00
443.50
0.3622
0.3706
50
19
1.80
9.00
435.80
0.3727
0.3819
70
7
3.55
10.65
621.10
0.2586
0.2646
70
19
2.10
10.50
593.20
0.2738
0.2806
95
19
2.50
12.50
840.70
0.1932
0.1980
100
7
4.30
12.90
911.20
0.1763
0.1810
120
19
2.80
14.00
1055.00
0.1540
0.1578
125
19
2.90
14.50
1131.00
0.1436
0.1471
150
19
3.20
16.00
1377.00
0.1180
0.1208
150
37
2.25
15.75
1334.00
0.1233
0.1264
185
19
3.55
17.75
1695.00
0.09582
0.09815
185
37
2.50
17.50
1647.00
0.09981
0.1024