Covered Line Cables meet or exceed all applicable requirements of ICEA S-70-547.
Product Details
Application
These cables are intended primary for the distribution of electrical energy under normal condition of overhead (aerial) installation and service outdoors. Approved for use on insulators for overhead circuits. Otherwise treated as a bare conductor.
Applicable Standard
ICEA S-70-5 47: Weather- Resistant Polyolefin Covered Wire and Cable.
ASTM B232: Specification for Concentric-Lay-Stranded Aluminum Conductors, Coated-Steel Reinforced (ACSR).
ASTM B399: Specification for Concentric-Lay-Stranded Aluminum Alloy 6201-T81 Conductors.
Cable Construction
Conductor Aluminum alloy 1350-H19 stranded per ASTM B231 or ACSR stranded per ASTM B232 or AAAC stranded per ASTM B399.
Separator A suitable opaque tape, as required.
Insulation Black thermoset cross-linked polyethylene (XLPE) or thermoplastic high density polyethylene (HDPE).
Technical Data
Code
Word
Size AWG or Kcmil
Number of strands
Insulation
Thickness
mil
Cable
OD
in
Rated
Strength
lb
Weight
PE
lb/kft
Weight
XLPE
lb/kft
Walnut
6
6/1
30
0.25
1131
47
46
Butternut
4
6/1
30
0.30
1767
71
70
Hickory
4
7/1
30
0.32
2242
82
82
Pignut
2
6/1
45
0.39
2708
116
115
Beech
2
7/1
45
0.42
3458
135
134
Almond
1/0
6/1
60
0.50
4161
188
186
Pecan
2/0
6/1
60
0.55
5035
232
229
Cottonwood
2/0
6/1
80
0.59
5035
247
247
Fibert
3/0
6/1
60
0.60
6289
286
283
Chokeberry
3/0
6/1
80
0.64
6289
303
300
Buckeye
4/0
6/1
60
0.65
7933
353
351
Gumwood
4/0
6/1
80
0.70
7933
372
369
Hackberry
266.8
18/1
60
0.72
6536
356
353
Redbud
266.8
18/1
80
0.76
6536
377
373
Mockernut
336.4
18/1
60
0.79
8246
441
438
Aspen
336.4
18/1
80
0.83
8246
464
460
Application
These cables are intended primary for the distribution of electrical energy under normal condition of overhead (aerial) installation and service outdoors. Approved for use on insulators for overhead circuits. Otherwise treated as a bare conductor.
Applicable Standard
ICEA S-70-5 47: Weather- Resistant Polyolefin Covered Wire and Cable.