Concentric strand or compressed 1350-H19 conductor, polyethylene or cross-linked polyethylene insulation, concentric strand AAC, ACSR, or 6201 alloy neutral messenger.
Product Details
Application To supply 120 volt aerial service for temporary service at construction sites, outdoor or street lighting. For service at 600 volts or lower at a conductor temperature of 75°C maximum.
Applicable Standard
ASTM B 230
ASTM B 231
ASTM B 232
ASTM B 233
ICEA S-66-524 (NEMA WC7)
Construction Concentric strand or compressed 1350-H19 conductor, polyethylene or cross-linked polyethylene insulation, concentric strand AAC, ACSR, or 6201 alloy neutral messenger.
Technical Data
Code Name
Conductor Assembly
Phase Conductor (AAC)
Messenger (ACSR)
Approx Cable Weight
D.C. Resistance at 20°C
Size
Stranding & Wire Dia
Insulation Thickness
Size
Stranding & Wire Dia
Aluminum
Steel
Phase
Messenger
AWG
no./mm
mis/mm
AWG
no./mm
no./mm
kg/km
ohm/km
ohm/km
D-11
DUPLEX
6
7/1.56
45/1.143
6
6/1.68
1/1.68
114
2.169
2.157
D-12
DUPLEX
3
7/2.2
45/1.143
3
6/2.38
1/2.38
212
1.076
1.074
D-14
QUADRUPLEX
3
7/2.2
45/1.143
3
6/2.38
1/2.38
420
1.076
1.074
D-15
QUADRUPLEX
1/0
7/3.12
60/1.524
1/0
6/3.37
1/3.37
835
0.5372
0.535
D-20
QUADRUPLEX
4
7/1.96
45/1.143
4
6/2.12
1/2.12
340
1.3620
1.3560
D-24
QUADRUPLEX
4/0
7/4.42
60/1.524
4/0
6/4.77
1/4.77
1580
0.2688
0.2676
D-25
QUADRUPLEX
6
7/1.56
45/1.143
6
6/1.68
1/1.68
230
2.1690
2.1570
Application To supply 120 volt aerial service for temporary service at construction sites, outdoor or street lighting. For service at 600 volts or lower at a conductor temperature of 75°C maximum.
Applicable Standard
ASTM B 230
ASTM B 231
ASTM B 232
ASTM B 233
ICEA S-66-524 (NEMA WC7)
Construction Concentric strand or compressed 1350-H19 conductor, polyethylene or cross-linked polyethylene insulation, concentric strand AAC, ACSR, or 6201 alloy neutral messenger.