Aerial Bundled Cable is designed for residential and rural areas for reducing the bushfire hazards.
Product Details
Application Aerial Bundled Cable is designed for residential and rural areas for reducing the bushfire hazards. The XLPE covering contains a high level of carbon black for UV resistance. It is designed for where reliability, safety and low installation cost are required, but it is only for short spans due to increased weight.
Applicable Standard NF C 33-209
Cable Construction
Phase Conductor (AAC Compacted) All conductors shall be constructed to IEC 61089. The properties of the Aluminium wires before stranding shall be as below.
Tensile strength not less than
90 N/mm2
Resistivity at 20°C not exceeding
0.02845 ohm/mm²/m
Netural Conductor (AAAC Non-Compacted) The neutral shall be an All-Aluminium-Alloy conductor composed of wires drawn from rod, which is manufactured in a continuous casting and rolling procedure. The properties for the individual wires before stranding shall be
Tensile strength not less than
278 N/mm²
Resistivity at 20°C not exceeding
0.0328 ohm/mm²/m
Insulation The Insulating Material shall be of black weather resistant cross linked thermosetting polyethylene (XLPE) conforming to IEC60502/IEC60811/ ASTM D 1603 and it shall be fully pressure extruded on the bare conductors of the phases / street lamp / neutral.
Dimenison Characteristics
Article
Unit
Offered Value
ABC Twisted cable 3x35 mm² + 1x54,6 Alec
Standard
NFC 33209 or equivalent
Material
ALUMINIUM
section
mm²
50
number of cores
n
7
Min Diameter
mm
7.9
Max Diameter
mm
8.4
Max Linear resistance of CC at 20°C
Ohm/km
0.641
Breaking load
daN
620
Neutral/support Conductor of
material
ALMELEC
section
mm²
54.6
number of cores
n
7
Min Diameter
mm
9.2
Max Diameter
mm
9.6
Max Linear resistance of CC at 20°C
Ohm/km
0.63
Breaking load
daN
1660
Insulating Sheath thickness
mm
1.6
Overall Diameter of cable
mm
12.3 to 13
Application Aerial Bundled Cable is designed for residential and rural areas for reducing the bushfire hazards. The XLPE covering contains a high level of carbon black for UV resistance. It is designed for where reliability, safety and low installation cost are required, but it is only for short spans due to increased weight.
Applicable Standard NF C 33-209
Cable Construction
Phase Conductor (AAC Compacted) All conductors shall be constructed to IEC 61089. The properties of the Aluminium wires before stranding shall be as below.
Tensile strength not less than
90 N/mm2
Resistivity at 20°C not exceeding
0.02845 ohm/mm²/m
Netural Conductor (AAAC Non-Compacted) The neutral shall be an All-Aluminium-Alloy conductor composed of wires drawn from rod, which is manufactured in a continuous casting and rolling procedure. The properties for the individual wires before stranding shall be
Tensile strength not less than
278 N/mm²
Resistivity at 20°C not exceeding
0.0328 ohm/mm²/m
Insulation The Insulating Material shall be of black weather resistant cross linked thermosetting polyethylene (XLPE) conforming to IEC60502/IEC60811/ ASTM D 1603 and it shall be fully pressure extruded on the bare conductors of the phases / street lamp / neutral.