PVC INSULATED LAID UP AND PVC SHEATHED CABLE TO AS/NZS 5000.1
Product Details
Application For mains, submains and subcircuits unenclosed, in conduit, buried direct or in underground ducts for buildings and industrial plants where not subject to mechanical damage and where out of balance currents may require a neutral equal in size to the active.
Applicable Standard AS/NZS 5000.1
Characteristics Voltage Rating Uo/U: 0.6/1 kV Maximum continuous operating temperature: 75 °C Can also be operated at temperatures up to 90 °C when not exposed to mechanical deformation (see AS/NZS 3008.1) Minimum Bending Radius: Fixed: 12 x Overall Diameter (O.D.)
Cable Construction Conductor Material: Copper Wire Insulation: V-90 PVC Outer sheath: 5V-90 PVC Type of conductor: stranded copper With Green/Yellow Core: Yes With smaller neutral conductor: No
Dimension Characteristics
Conductor
Cable
Nominal C.S.A. mm2
Number and diameter of wires No./mm
Nominal diameter mm
Nominal insulation thickness mm
Minimum
Maximum
Approx. mass kg/100m
Min. Installed bending radius mm
1.5
7/0.50
1.5
0.8
11.8
12.2
22
50
2.5
7/0.67
2.0
0.8
13.3
13.7
30
55
4
7/0.85
2.6
1.0
15.3
15.8
40
65
6
7/1.04
3.1
1.0
16.5
17.1
48
70
10
7/1.35
4.1
1.0
19.5
20.3
71
80
16
7/1.70
5.1
1.0
22.1
22.9
100
90
25
19/1.35
6.8
1.2
25.6
26.4
144
160
35
19/1.53
7.7
1.2
28.5
29.5
189
180
50
19/1.78
8.9
1.4
33.1
34.3
258
210
70
19/2.14
10.7
1.4
38.0
39.0
353
240
95
19/2.45
12.5
1.6
43.3
44.6
474
270
120
37/2.03
14.2
1.6
47.6
48.8
585
300
150
37/2.25
15.8
1.8
53.1
54.6
729
330
185
37/2.52
17.6
2.0
59.1
60.7
910
360
240
61/2.25
20.3
2.2
67.3
69.1
1195
410
300
61/2.52
22.7
2.4
74.6
76.6
1487
460
Application For mains, submains and subcircuits unenclosed, in conduit, buried direct or in underground ducts for buildings and industrial plants where not subject to mechanical damage and where out of balance currents may require a neutral equal in size to the active.
Applicable Standard AS/NZS 5000.1
Characteristics Voltage Rating Uo/U: 0.6/1 kV Maximum continuous operating temperature: 75 °C Can also be operated at temperatures up to 90 °C when not exposed to mechanical deformation (see AS/NZS 3008.1) Minimum Bending Radius: Fixed: 12 x Overall Diameter (O.D.)
Cable Construction Conductor Material: Copper Wire Insulation: V-90 PVC Outer sheath: 5V-90 PVC Type of conductor: stranded copper With Green/Yellow Core: Yes With smaller neutral conductor: No