It can be safely deployed in most applications where mechanical stresses are not anticipated – indoors, outdoors, direct burial underground, in concrete, or submerged in water.
Product Details
Application Power and control cable for fixed installation. Can be used indoors, outdoors, underground, in concrete and in water.
Applicable Standard IEC 60228
IEC 60502-1
Characteristics Voltage Rating Uo/U: 0.6/1 kV Temperature Rating: Fixed: -15°C to + 70°C Flexed: -15°C to + 50°C Minimum Bending Radius: Fixed: 12 x Overall Diameter (O.D.)
Cable Construction Conductor RE: Class 1 solid copper conductor RM: Class 2 stranded copper conductor
Insulation PVC (Polyvinyl Chloride)
Filler PP Rope
Sheath PVC (Polyvinyl Chloride)
Dimension Characteristics
Section
Insulation Thickness
Sheath Thickness
Overall Diameter
Cable Weight
DC. Electrical Resistance at 20°C
No.xmm2
mm
mm
mm
Cu
Al
Cu
Al
kg/km
Ω/km
2x0.5
0.8
1.8
9.6
93
-
36.0
-
2x0.75
0.8
1.8
10.0
103
-
24.9
-
2x1.5
0.8
1.8
10.8
129
110
12.1
18.1
2x2.5
0.8
1.8
11.6
158
127
7.41
12.1
2x4
1.0
1.8
13.4
218
168
4.61
7.41
2x6
1.0
1.8
14.4
272
196
3.08
4.61
2x10
1.0
1.8
17.0
392
265
1.83
3.08
2x16
1.0
1.8
19.0
536
335
1.15
1.91
2x25
1.2
1.8
22.4
781
465
0.727
1.20
2x35
1.2
1.8
23.6
974
541
0.524
0.868
2x50
1.4
1.8
27.0
1286
700
0.387
0.641
2x70
1.4
1.9
30.2
1750
901
0.268
0.443
2x95
1.6
2.0
34.6
2371
1192
0.193
0.320
2x120
1.6
2.1
37.8
2917
1431
0.153
0.253
2x150
1.8
2.2
41.8
3579
1744
0.124
0.206
2x185
2.0
2.4
46.2
4445
2150
0.0991
0.164
2x240
2.2
2.6
52.0
5762
2745
0.0754
0.125
2x300
2.4
2.7
57.4
7142
3357
0.0601
0.100
2x400
2.6
3.0
64.6
9079
4239
0.0470
0.0778
2x500
2.8
3.2
71.8
11503
5287
0.0366
0.0605
Application Power and control cable for fixed installation. Can be used indoors, outdoors, underground, in concrete and in water.
Applicable Standard IEC 60228
IEC 60502-1
Characteristics Voltage Rating Uo/U: 0.6/1 kV Temperature Rating: Fixed: -15°C to + 70°C Flexed: -15°C to + 50°C Minimum Bending Radius: Fixed: 12 x Overall Diameter (O.D.)
Cable Construction Conductor RE: Class 1 solid copper conductor RM: Class 2 stranded copper conductor