It can be safely deployed in most applications where mechanical stresses are not anticipated – indoors, outdoors, direct burial underground, in concrete, or submerged in water.
Product Details
Application Power and control cable for fixed installation. Can be used indoors, outdoors, underground, in concrete and in water.
ApplicableStandard
IEC 60228
IEC 60502-1
Characteristics
Voltage Rating Uo/U: 0.6/1 kV Temperature Rating: Fixed: -15°C to + 70°C Flexed: -15°C to + 50°C Minimum Bending Radius: Fixed: 12 x Overall Diameter (O.D.)
Cable Construction
Conductor
RE: Class 1 solid copper conductor RM: Class 2 stranded copper conductor
Insulation PVC (Polyvinyl Chloride)
Filler PP Rope
Sheath PVC (Polyvinyl Chloride)
Dimension Characteristics
Section
Insulation Thickness
Sheath Thickness
Overall Diameter
Cable Weight
DC. Electrical Resistance at 20°C
No.xmm2
mm
mm
mm
Cu
Al
Cu
Al
kg/km
Ω/km
1x0.5
0.8
1.4
5.2
37
-
36.0
-
1x0.75
0.8
1.4
5.4
41
-
24.9
-
1x1.5
0.8
1.4
5.8
52
43
12.1
18.1
1x2.5
0.8
1.4
6.2
65
50
7.41
12.1
1x4
1.0
1.4
7.1
90
66
4.61
7.41
1x6
1.0
1.4
7.6
114
77
3.08
4.61
1x10
1.0
1.4
8.9
166
103
1.83
3.08
1x16
1.0
1.4
9.9
230
131
1.15
1.91
1x25
1.2
1.4
11.6
338
182
0.727
1.20
1x35
1.2
1.4
12.2
428
214
0.524
0.868
1x50
1.4
1.4
13.9
565
276
0.387
0.641
1x70
1.4
1.5
15.6
778
360
0.268
0.443
1x95
1.6
1.5
17.7
1050
470
0.193
0.320
1x120
1.6
1.6
19.4
1299
567
0.153
0.253
1x150
1.8
1.6
21.3
1587
683
0.124
0.206
1x185
2.0
1.6
23.5
1970
839
0.0991
0.164
1x240
2.2
1.7
26.4
2555
1069
0.0754
0.125
1x300
2.4
1.8
29.2
3178
1313
0.0601
0.100
1x400
2.6
1.9
32.7
4025
1641
0.0470
0.0778
1x500
2.8
2.0
36.3
5110
2048
0.0366
0.0605
1x630
2.8
2.1
40.0
6296
2537
0.0283
0.0469
1x800
2.8
2.2
44.2
8203
3133
0.0221
0.0367
Application Power and control cable for fixed installation. Can be used indoors, outdoors, underground, in concrete and in water.
ApplicableStandard
IEC 60228
IEC 60502-1
Characteristics
Voltage Rating Uo/U: 0.6/1 kV Temperature Rating: Fixed: -15°C to + 70°C Flexed: -15°C to + 50°C Minimum Bending Radius: Fixed: 12 x Overall Diameter (O.D.)
Cable Construction
Conductor
RE: Class 1 solid copper conductor RM: Class 2 stranded copper conductor