Power and auxiliary control cables for use in power networks, underground, outdoor and indoor applications and for use in cable ducting.
Product Details
Description Electric cable with copper conductors, XLPE insulation, PVC bedding, galvanized steel tape armour (STA) and PVC outer sheath
Application Multi-core PVC cable with steel tape armour (STA). Power and auxiliary control cables for use in power networks, underground, outdoor and indoor applications and for use in cable ducting.
Applicable Standard IEC 60228
IEC 60502-1
Cable Construction Conductor: Compact stranded copper conductor, Cl.2 as per IEC 60228
Insulation: XLPE(cross-linked polyethylene) rated at 90 OC
Inner sheath: PVC
Armored: Galvanized Steel Tape.
Sheath: PVC or FR-PVC type ST2 to IEC 60502, black
Dimension Characteristics
Section
Insulation Thickness
Sheath Thickness
Overall Diameter
Cable Weight
DC. Electrical Resistance at 20°C
No.xmm2
mm
mm
mm
Cu
Al
Cu
Al
kg/km
Ω/km
2x4
0.7
1.8
13.6
285
235
4.61
7.41
2x6
0.7
1.8
14.6
346
270
3.08
4.61
2x10
0.7
1.8
17.2
482
356
1.83
3.08
2x16
0.7
1.8
19.2
641
439
1.15
1.91
2x25
0.9
1.8
22.6
904
588
0.727
1.20
2x35
0.9
1.8
23.8
1105
672
0.524
0.868
2x50
1.0
1.8
26.8
1416
830
0.387
0.641
2x70
1.1
1.9
30.4
1915
1067
0.268
0.443
2x95
1.1
2.0
34.0
2514
1336
0.193
0.320
2x120
1.2
2.1
38.8
3465
1978
0.153
0.253
2x150
1.4
2.3
43.0
4197
2362
0.124
0.206
2x185
1.6
2.4
47.2
5098
2802
0.0991
0.164
2x240
1.7
2.6
52.6
6453
3436
0.0754
0.125
2x300
1.8
2.7
57.6
7861
4076
0.0601
0.100
2x400
2.0
3.0
64.8
9875
5036
0.0470
0.0778
2x500
2.2
3.2
72.0
12374
6159
0.0366
0.0605
3x4
0.7
1.8
14.2
338
263
4.61
7.41
3x6
0.7
1.8
15.3
419
308
3.08
4.61
3x10
0.7
1.8
18.1
598
408
1.83
3.08
3x16
0.7
1.8
20.2
811
509
1.15
1.91
3x25
0.9
1.8
23.9
1168
693
0.727
1.20
3x35
0.9
1.8
25.2
1455
805
0.524
0.868
3x50
1.0
1.8
28.4
1883
1003
0.387
0.641
3x70
1.1
1.9
32.3
2580
1307
0.268
0.443
3x95
1.1
2.1
36.4
3439
1671
0.193
0.320
3x120
1.2
2.2
41.5
4650
2420
0.153
0.253
3x150
1.4
2.4
46.0
5652
2901
0.124
0.206
3x185
1.6
2.5
50.5
6906
3463
0.0991
0.164
3x240
1.7
2.7
56.3
8802
4277
0.0754
0.125
3x300
1.8
2.9
61.9
10810
5133
0.0601
0.100
3x400
2.0
3.1
69.4
13590
6330
0.0470
0.0778
3x500
2.2
3.3
77.1
17109
7786
0.0366
0.0605
4x4
0.7
1.8
15.2
400
300
4.61
7.41
4x6
0.7
1.8
16.4
504
352
3.08
4.61
4x10
0.7
1.8
19.5
728
475
1.83
3.08
4x16
0.7
1.8
21.9
1004
602
1.15
1.91
4x25
0.9
1.8
26.0
1461
827
0.727
1.20
4x35
0.9
1.8
27.5
1837
971
0.524
0.868
4x50
1.0
1.9
31.3
2405
1233
0.387
0.641
4x70
1.1
2.0
35.6
3312
1615
0.268
0.443
4x95
1.1
2.2
41.4
4827
2470
0.193
0.320
4x120
1.2
2.4
45.9
5952
2979
0.153
0.253
4x150
1.4
2.5
50.7
7227
3558
0.124
0.206
4x185
1.6
2.7
55.9
8878
4287
0.0991
0.164
4x240
1.7
2.9
62.4
11353
5320
0.0754
0.125
4x300
1.8
3.1
68.6
13970
6400
0.0601
0.100
4x400
2.0
3.4
77.2
17631
7951
0.0470
0.0778
4x500
2.2
3.7
87.2
23128
10698
0.0366
0.0605
Description Electric cable with copper conductors, XLPE insulation, PVC bedding, galvanized steel tape armour (STA) and PVC outer sheath
Application Multi-core PVC cable with steel tape armour (STA). Power and auxiliary control cables for use in power networks, underground, outdoor and indoor applications and for use in cable ducting.
Applicable Standard IEC 60228
IEC 60502-1
Cable Construction Conductor: Compact stranded copper conductor, Cl.2 as per IEC 60228
Insulation: XLPE(cross-linked polyethylene) rated at 90 OC
Inner sheath: PVC
Armored: Galvanized Steel Tape.
Sheath: PVC or FR-PVC type ST2 to IEC 60502, black