Power and auxiliary control cables for use in power networks, underground, outdoor and indoor applications and for use in cable ducting.
Product Details
Description Electric cable with copper conductors, XLPE insulation, PVC bedding, galvanized steel wires armour (SWA) and PVC outer sheath
Application Multi-core PVC cable with steel wire armour (SWA). Power and auxiliary control cables for use in power networks, underground, outdoor and indoor applications and for use in cable ducting.
Applicable Standard IEC 60228
IEC 60502-1
Cable Construction Conductor: Compact stranded copper conductor, Cl.2 as per IEC 60228
Insulation: XLPE(cross-linked polyethylene) rated at 90 OC
Inner sheath: PVC
Armored: Galvanized Steel Wire.
Sheath: PVC or FR-PVC type ST2 to IEC 60502, black
Dimension Characteristics
Section
Insulation Thickness
Sheath Thickness
Overall Diameter
Cable Weight
DC. Electrical Resistance at 20°C
No.xmm2
mm
mm
mm
Cu
Al
Cu
Al
kg/km
Ω/km
2x4
0.7
1.8
16.8
447
397
4.61
7.41
2x6
0.7
1.8
17.8
520
444
3.08
4.61
2x10
0.7
1.8
21.3
835
708
1.83
3.08
2x16
0.7
1.8
23.3
1024
823
1.15
1.91
2x25
0.9
1.8
27.4
1512
1195
0.727
1.20
2x35
0.9
1.8
28.6
1740
1307
0.524
0.868
2x50
1.0
1.8
31.6
2136
1550
0.387
0.641
2x70
1.1
2.0
35.4
2735
1886
0.268
0.443
2x95
1.1
2.1
39.8
3697
2518
0.193
0.320
2x120
1.2
2.2
43.4
4396
2909
0.153
0.253
2x150
1.4
2.3
47.4
5208
3374
0.124
0.206
2x185
1.6
2.5
53.2
6747
4451
0.0991
0.164
2x240
1.7
2.7
58.6
8278
5261
0.0754
0.125
2x300
1.8
2.8
64.0
9912
6127
0.0601
0.100
2x400
2.0
3.1
71.2
12168
7328
0.0470
0.0778
2x500
2.2
3.3
80.1
15893
9678
0.0366
0.0605
3x4
0.7
1.8
17.4
505
430
4.61
7.41
3x6
0.7
1.8
18.5
598
485
3.08
4.61
3x10
0.7
1.8
22.2
966
776
1.83
3.08
3x16
0.7
1.8
24.3
1220
918
1.15
1.91
3x25
0.9
1.8
28.7
1803
1328
0.727
1.20
3x35
0.9
1.8
30.0
2133
1483
0.524
0.868
3x50
1.0
1.9
33.4
2658
1779
0.387
0.641
3x70
1.1
2.0
38.1
3716
2442
0.268
0.443
3x95
1.1
2.2
42.2
4692
2924
0.193
0.320
3x120
1.2
2.3
46.1
5649
3418
0.153
0.253
3x150
1.4
2.5
52.0
7239
4487
0.124
0.206
3x185
1.6
2.6
56.5
8634
5191
0.0991
0.164
3x240
1.7
2.8
62.7
10790
6265
0.0754
0.125
3x300
1.8
3.0
68.3
13016
7338
0.0601
0.100
3x400
2.0
3.2
75.8
16028
8768
0.0470
0.0778
3x500
2.2
3.5
85.4
20926
11603
0.0366
0.0605
4x4
0.7
1.8
18.4
580
480
4.61
7.41
4x6
0.7
1.8
20.5
839
688
3.08
4.61
4x10
0.7
1.8
23.6
1119
866
1.83
3.08
4x16
0.7
1.8
26.7
1599
1196
1.15
1.91
4x25
0.9
1.8
30.8
2151
1518
0.727
1.20
4x35
0.9
1.9
32.5
2584
1718
0.524
0.868
4x50
1.0
2.0
36.3
3254
2081
0.387
0.641
4x70
1.1
2.2
41.6
4558
2860
0.268
0.443
4x95
1.1
2.3
46.0
5827
3469
0.193
0.320
4x120
1.2
2.5
51.9
7540
4566
0.153
0.253
4x150
1.4
2.6
56.7
8993
5324
0.124
0.206
4x185
1.6
2.8
62.3
10871
6281
0.0991
0.164
4x240
1.7
3.0
68.8
13552
7519
0.0754
0.125
4x300
1.8
3.2
75.0
16379
8809
0.0601
0.100
4x400
2.0
3.5
85.3
21416
11736
0.0470
0.0778
4x500
2.2
3.8
94.1
26417
13986
0.0366
0.0605
Description Electric cable with copper conductors, XLPE insulation, PVC bedding, galvanized steel wires armour (SWA) and PVC outer sheath
Application Multi-core PVC cable with steel wire armour (SWA). Power and auxiliary control cables for use in power networks, underground, outdoor and indoor applications and for use in cable ducting.
Applicable Standard IEC 60228
IEC 60502-1
Cable Construction Conductor: Compact stranded copper conductor, Cl.2 as per IEC 60228
Insulation: XLPE(cross-linked polyethylene) rated at 90 OC
Inner sheath: PVC
Armored: Galvanized Steel Wire.
Sheath: PVC or FR-PVC type ST2 to IEC 60502, black