AAC. (all aluminum conductor), ACSR(aluminum conductor steel reinforced) type cable covered by XLPE, used for transmission and distribution lines in wood or industrial areas. The service voltage of all its applications varies with the thickness of the insulation, which is 15 kV, 25 kV and 35kV.
STANDARD:
IEC 60502-2
WORKING CONDITIONS
1) Rated voltage: 15kV 25kV, 35kV
2) The tallest work temperature of the cable conductor:
XLPE insulation cable:90oC;
3) During having a short (lasting less than 5 seconds), the maximum temperature:
XLPE insulated cables is 250oC;
4) During the cable lying, the ambient temperature must be above -20oC.
5) Bending radius allowance of the cable:
It should be no less than 4D for the cable with outer diameter less than 25mm;
It should be no less than 6D for the cable with outer diameter of 25mm or more.
CONSTRUCTION:
1) Conductors Aluminum, circular stranded and compacted confirming to IEC 60228 – Class 2
2) Insulation XLPE thermosetting material conforming to IEC 60502-2
SPECIFICATION:
15kV AAC
Nominal section (mm²)
Dia of conductors
Insulation Thickness (mm)
Overall diameter (mm)
Aprox. weight
(mm)
(kg/km)
35
7.1
3
13.1
185
50
8.3
3
14.3
228
70
9.9
3
15.9
302
95
11.8
3
17.8
388
120
13.2
3
19.2
467
150
14.3
3
20.3
549
185
16.3
3
22.3
671
240
18.5
3
24.5
841
300
20.5
3
26.5
1,019
25kV AAC
Nominal section (mm²)
Dia of conductors
Insulation Thickness (mm)
Overall diameter (mm)
Aprox. weight
(mm)
(kg/km)
35
7.1
4
15.1
226
50
8.3
4
16.3
273
70
9.9
4
17.9
351
95
11.8
4
19.8
443
120
13.2
4
21.2
526
150
14.3
4
22.3
611
185
16.3
4
24.3
739
240
18.5
4
26.5
916
300
20.5
4
28.5
1,099
35kV AAC
Nominal section (mm²)
Dia of conductors
Insulation Thickness (mm)
Overall diameter (mm)
Aprox. weight
(mm)
(kg/km)
35
7.1
7.6
22.2
429
50
8.3
7.6
23.4
503
70
9.9
7.6
25
600
95
11.8
7.6
26.9
714
120
13.2
7.6
28.3
813
150
14.3
7.6
29.4
911
185
16.3
7.6
31.4
1062
240
18.5
7.6
33.6
1264
300
20.5
7.6
35.6
1,470
INSULATED OVERHEAD CONDUCTORS -15KV, 25KV, 35KV
APPLICATION
AAC. (all aluminum conductor), ACSR(aluminum conductor steel reinforced) type cable covered by XLPE, used for transmission and distribution lines in wood or industrial areas. The service voltage of all its applications varies with the thickness of the insulation, which is 15 kV, 25 kV and 35kV.
STANDARD:
IEC 60502-2
WORKING CONDITIONS
1) Rated voltage: 15kV 25kV, 35kV
2) The tallest work temperature of the cable conductor:
XLPE insulation cable:90oC;
3) During having a short (lasting less than 5 seconds), the maximum temperature:
XLPE insulated cables is 250oC;
4) During the cable lying, the ambient temperature must be above -20oC.
5) Bending radius allowance of the cable:
It should be no less than 4D for the cable with outer diameter less than 25mm;
It should be no less than 6D for the cable with outer diameter of 25mm or more.
CONSTRUCTION:
1) Conductors Aluminum, circular stranded and compacted confirming to IEC 60228 – Class 2
2) Insulation XLPE thermosetting material conforming to IEC 60502-2