0.6/1kV CAAI-S Cable with / without Public Lighting
Application
The product is a new type of aerial cable for power transmission. It is extensively used in overhead power transmission line. It improves the safety and reliance of electrified wire netting.
Standard:
IEC 60228: Conductors of insulated cables.
ASTM A 475: Zinc coated steel wire strand.
NTP-IEC 60228: Conductors of insulated cables.
NTP 370.254: Cables for overhead distribution networks self-supporting XLPE insulated of rated voltages up to and including 0.6/1 kV.
Working conditions of aerial insulation power cable
1) Rated voltage: 0.6-1kV
2) The tallest work temperature of the cable conductor:XLPE insulation cable:90oC;
3) During having a short (lasting less than 5 seconds), the maximum temperature: XLPE insulated cables is 250oC;
4) During the cable lying, the ambient temperature must be above -20oC.
5) Bending radius allowance of the cable:
It should be no less than 4D for the cable with outer diameter less than 25mm;
It should be no less than 6D for the cable with outer diameter of 25mm or more.
Construction:
1. Conductor: Aluminium 1350, class 2.
2. Insulation: Cross linked polyethylene XLPE.
3. Public lighting: Aluminium 1350 insulated with cross-linked polyethylene XLPE.
4. Messenger: Galvanized stranded steel wire insulated with cross-linked polyethylene XLPE.
The specification of cable
| Model | Phase | Lighting | Overall Dia. |
| No of Phase | Section Area | No of strands x dia | Insulation Thickness | Max resistance at 20 ºC | Section Area | Max resistance at 20 ºC |
|
| mm | mm | mm | ohm/km |
| ohm/km | mm |
|
| 2X16 | 2 | 16 | 7x1.03 | 1,14 | 1,910 | -- | -- | 16 |
| 2X25 | 2 | 25 | 7x1.20 | 1,14 | 1,200 | -- | -- | 18 |
| 2X35 | 2 | 35 | 7x1.20 | 1,14 | 0,868 | -- | -- | 19 |
| 2X50 | 2 | 50 | 7x2,03 | 1,52 | 0,641 | -- | -- | 23 |
| 2X70 | 2 | 70 | 7x2,03 | 1,52 | 0,443 | -- | -- | 27 |
| 2X95 | 2 | 95 | 7x2,03 | 1,52 | 0,320 | -- | -- | 31 |
| 2X120 | 2 | 120 | 7x2,03 | 2,03 | 0,253 | -- | -- | 34 |
|
| 2X25+1x16 | 2 | 25 | 7x1.20 | 1,14 | 1,200 | 16 | 1,910 | 18 |
| 2X35+1x16 | 2 | 35 | 7x1.20 | 1,14 | 0,868 | 16 | 1,910 | 19 |
| 2X50+1x16 | 2 | 50 | 7x2,03 | 1,52 | 0,641 | 16 | 1,910 | 23 |
| 2X70+1x16 | 2 | 70 | 7x2,03 | 1,52 | 0,443 | 16 | 1,910 | 27 |
| 2X95+1x16 | 2 | 95 | 7x2,03 | 1,52 | 0,320 | 16 | 1,910 | 31 |
| 2X120+1x16 | 2 | 120 | 7x2,03 | 2,03 | 0,253 | 16 | 1,910 | 34 |
|
| 3X16 | 3 | 16 | 7x1.03 | 1,14 | 1,910 | -- | -- | 16 |
| 3X25 | 3 | 25 | 7x1.20 | 1,14 | 1,200 | -- | -- | 18 |
| 3X35 | 3 | 35 | 7x1.20 | 1,14 | 0,868 | -- | -- | 19 |
| 3X50 | 3 | 50 | 7x2,03 | 1,52 | 0,641 | -- | -- | 23 |
| 3X70 | 3 | 70 | 7x2,03 | 1,52 | 0,443 | -- | -- | 27 |
| 3X95 | 3 | 95 | 7x2,03 | 1,52 | 0,320 | -- | -- | 31 |
| 3X120 | 3 | 120 | 7x2,03 | 2,03 | 0,253 | -- | -- | 34 |
|
| 3X16+1x16 | 3 | 16 | 7x1.03 | 1,14 | 1,910 | 16 | 1,910 | 16 |
| 3X25+1x16 | 3 | 25 | 7x1.20 | 1,14 | 1,200 | 16 | 1,910 | 18 |
| 3X25+2x16 | 3 | 25 | 7x1.20 | 1,14 | 1,200 | 16 | 1,910 | 18 |
| 3X35+1x16 | 3 | 35 | 7x1.20 | 1,14 | 0,868 | 16 | 1,910 | 19 |
| 3X50+1x16 | 3 | 50 | 7x2,03 | 1,52 | 0,641 | 16 | 1,910 | 23 |
| 3X70+1x16 | 3 | 70 | 7x2,03 | 1,52 | 0,443 | 16 | 1,910 | 27 |
| 3X95+1x16 | 3 | 95 | 7x2,03 | 1,52 | 0,320 | 16 | 1,910 | 31 |
| 3X120+1x16 | 3 | 120 | 7x2,03 | 2,03 | 0,253 | 16 | 1,910 | 34 |
0.6/1kV CAAI-S Cable with / without Public Lighting
Application
The product is a new type of aerial cable for power transmission. It is extensively used in overhead power transmission line. It improves the safety and reliance of electrified wire netting.
Standard:
IEC 60228: Conductors of insulated cables.
ASTM A 475: Zinc coated steel wire strand.
NTP-IEC 60228: Conductors of insulated cables.
NTP 370.254: Cables for overhead distribution networks self-supporting XLPE insulated of rated voltages up to and including 0.6/1 kV.
Working conditions of aerial insulation power cable
1) Rated voltage: 0.6-1kV
2) The tallest work temperature of the cable conductor:XLPE insulation cable:90oC;
3) During having a short (lasting less than 5 seconds), the maximum temperature: XLPE insulated cables is 250oC;
4) During the cable lying, the ambient temperature must be above -20oC.
5) Bending radius allowance of the cable:
It should be no less than 4D for the cable with outer diameter less than 25mm;
It should be no less than 6D for the cable with outer diameter of 25mm or more.
Construction:
1. Conductor: Aluminium 1350, class 2.
2. Insulation: Cross linked polyethylene XLPE.
3. Public lighting: Aluminium 1350 insulated with cross-linked polyethylene XLPE.
4. Messenger: Galvanized stranded steel wire insulated with cross-linked polyethylene XLPE.
The specification of cable
| Model | Phase | Lighting | Overall Dia. |
| No of Phase | Section Area | No of strands x dia | Insulation Thickness | Max resistance at 20 ºC | Section Area | Max resistance at 20 ºC |
|
| mm | mm | mm | ohm/km |
| ohm/km | mm |
|
| 2X16 | 2 | 16 | 7x1.03 | 1,14 | 1,910 | -- | -- | 16 |
| 2X25 | 2 | 25 | 7x1.20 | 1,14 | 1,200 | -- | -- | 18 |
| 2X35 | 2 | 35 | 7x1.20 | 1,14 | 0,868 | -- | -- | 19 |
| 2X50 | 2 | 50 | 7x2,03 | 1,52 | 0,641 | -- | -- | 23 |
| 2X70 | 2 | 70 | 7x2,03 | 1,52 | 0,443 | -- | -- | 27 |
| 2X95 | 2 | 95 | 7x2,03 | 1,52 | 0,320 | -- | -- | 31 |
| 2X120 | 2 | 120 | 7x2,03 | 2,03 | 0,253 | -- | -- | 34 |
|
| 2X25+1x16 | 2 | 25 | 7x1.20 | 1,14 | 1,200 | 16 | 1,910 | 18 |
| 2X35+1x16 | 2 | 35 | 7x1.20 | 1,14 | 0,868 | 16 | 1,910 | 19 |
| 2X50+1x16 | 2 | 50 | 7x2,03 | 1,52 | 0,641 | 16 | 1,910 | 23 |
| 2X70+1x16 | 2 | 70 | 7x2,03 | 1,52 | 0,443 | 16 | 1,910 | 27 |
| 2X95+1x16 | 2 | 95 | 7x2,03 | 1,52 | 0,320 | 16 | 1,910 | 31 |
| 2X120+1x16 | 2 | 120 | 7x2,03 | 2,03 | 0,253 | 16 | 1,910 | 34 |
|
| 3X16 | 3 | 16 | 7x1.03 | 1,14 | 1,910 | -- | -- | 16 |
| 3X25 | 3 | 25 | 7x1.20 | 1,14 | 1,200 | -- | -- | 18 |
| 3X35 | 3 | 35 | 7x1.20 | 1,14 | 0,868 | -- | -- | 19 |
| 3X50 | 3 | 50 | 7x2,03 | 1,52 | 0,641 | -- | -- | 23 |
| 3X70 | 3 | 70 | 7x2,03 | 1,52 | 0,443 | -- | -- | 27 |
| 3X95 | 3 | 95 | 7x2,03 | 1,52 | 0,320 | -- | -- | 31 |
| 3X120 | 3 | 120 | 7x2,03 | 2,03 | 0,253 | -- | -- | 34 |
|
| 3X16+1x16 | 3 | 16 | 7x1.03 | 1,14 | 1,910 | 16 | 1,910 | 16 |
| 3X25+1x16 | 3 | 25 | 7x1.20 | 1,14 | 1,200 | 16 | 1,910 | 18 |
| 3X25+2x16 | 3 | 25 | 7x1.20 | 1,14 | 1,200 | 16 | 1,910 | 18 |
| 3X35+1x16 | 3 | 35 | 7x1.20 | 1,14 | 0,868 | 16 | 1,910 | 19 |
| 3X50+1x16 | 3 | 50 | 7x2,03 | 1,52 | 0,641 | 16 | 1,910 | 23 |
| 3X70+1x16 | 3 | 70 | 7x2,03 | 1,52 | 0,443 | 16 | 1,910 | 27 |
| 3X95+1x16 | 3 | 95 | 7x2,03 | 1,52 | 0,320 | 16 | 1,910 | 31 |
| 3X120+1x16 | 3 | 120 | 7x2,03 | 2,03 | 0,253 | 16 | 1,910 | 34 |